PD6800-0L1 Explosion-Proof Loop-Powered Process Meter
Instruction Manual
6
Product Ratings and Approvals
FM
Explosion-proof for use in:
Class I, Division 1, Groups B, C and D
Dust-ignition proof for use in:
Class II/III, Division 1, Groups E, F and G; T6
Flame-proof for use in:
Class I, Zone 1, AEx d Group IIC; T6
Protection by Enclosure:
Zone 21, AEx tb IIIC; T85°C
Ta = -40 to 75°C.
Enclosure: Type 4X, IP66.
Certificate number: 3040391
CSA
Explosion-proof for use in:
Class I, Division 1, Groups B, C and D
Dust-ignition proof for use in:
Class II/III, Division 1, Groups E, F and G; T6
Flame-proof for use in:
Zone 1, Ex d IIC T6
Ta = -40 to 75°C.
Enclosure: Type 4X & IP66/IP68.
Certificate number: 2325749
ATEX
II 2 G D. Flame-proof for use in:
Zone 1, Ex d IIC T6 Gb
Protection by Enclosure for use in:
Dust Atmospheres (Zone 21)
Ex tb IIIC T85°C Db IP68.
Ta = -40°C to +75°C
Certificate number: Sira 10ATEX1116X
IECEx
Flame-proof for use in:
Zone 1, Ex d IIC T6 Gb
Protection by Enclosure for use in:
Dust Atmospheres (Zone 21)
Ex tb IIIC T85°C Db IP68.
Ta = -40°C to +75°C
Certificate number: IECEx SIR 10.0056X
Special Conditions for Safe Use:
Use suitably certified and dimensioned cable entry
device and/or plug. The equipment shall be installed
such that the supply cable is protected from mechani-
cal damage. The cable shall not be subjected to ten-
sion or torque. If the cable is to be terminated within
an explosive atmosphere, then appropriate protection
of the free end of the cable shall be provided.
Year of Construction:
This information is contained within the serial number
with the first four digits representing the year and
month in the YYMM format.
For European Community:
The PD6800-0L1 must
be installed in accordance with the ATEX directive
94/9/EC, and the product certificate Sira
10ATEX1116X.
Electromagnetic Compatibility
Emissions
EN 61326:2013
Safety requirements for measurement,
control, and laboratory use – Industrial
Group 1 Class A ISM emissions
requirements
Radiated
Emissions
Class A
Immunity
EN 61326:2013
Safety requirements for measurement,
control, and laboratory use
ESD
±4 kV contact, ±8 kV air
RFI –
Amplitude
Modulated
80-1000 MHz @ 10 V/m,
1.4-2.0 GHz @ 3 V/m,
2.0-2.7 GHz @ 1 V/m,
80% AM (1 kHz)
EFT
±2 kV DC mains, ±1 kV other
Telco Surge
±1 kV
CRFI
3 V, 0.15-80 MHz, 1 kHz 80% AM
Safety Information
•
Read complete instructions prior to installation
and operation of the meter.
•
Installation and service should be performed only
by trained service personnel. Service requiring
replacement of internal components must be
performed at the factory.
•
Disconnect from supply before opening
enclosure. Keep cover tight while circuits are
alive. Conduit seals must be installed within
18" (450mm) of the enclosure.
•
Verify that the operating atmosphere of the meter
is consistent with the appropriate hazardous
locations certifications.
•
If the meter is installed in a high voltage
environment and a fault or installation error
occurs, high voltage may be present on any lead.