PD663 Explosion-Proof Loop-Powered Meter
Instruction Manual
4
Specifications
Except where noted all specifications apply to operation at +25°C.
General
Display
0.6" (15.2 mm) LCD, 3½+ digits;
-1999 to 2999
Display
Update Rate
2 Updates/Second
Overrange
Display flashes
2999
Underrange
Display flashes
-1999
Programming
Method
Four internal pushbuttons
Noise Filter
Programmable
HI
,
LO
, or
OFF
Recalibration
Recalibration is recommended at least every
12 months.
Max/Min
Display
Max/Min readings reached by the process are
stored until reset by the user or until power to
the meter is turned off.
Non-Volatile
Memory
All programmed settings are stored in
non-volatile memory for a minimum of
ten years if power is lost.
Normal Mode
Rejection
64 dB at 50/60 Hz
Environmental
Operating temperature range: -40 to 75°C
Storage temperature range: -40 to 75°C
Relative humidity: 0 to 90% non-condensing
Connections
Removable screw terminals accept
12 to 22 AWG wire
Enclosure
Explosion-proof die cast aluminum with glass
window, 0.30% max copper content, corrosion
resistant epoxy coating,
color: blue. NEMA 4X, 7, & 9, IP68.
Two ½" NPT threaded conduit openings.
One ½" NPT nickel plated brass conduit plug
with 10 mm hex key fitting installed.
Mounting
May be mounted directly to conduit.
Two mounting holes for 1.5" pipe or wall
on page
Tightening
Torque
Screw terminal electrical connectors:
4.5 lb-in (0.5 Nm)
Overall
Dimensions
4.84" x 4.29" x 3.62"
(123 mm x 109 mm x 92 mm)
(W x H x D)
Weight
2.45 lbs (40 oz, 1.13 kg)
Warranty
3 years parts and labor. See Warranty
Information and Terms & Conditions on
Input
Input
4-20 mA
Accuracy
±0.05% FS ±1 count
Function
Linear (2 to 32 points) or square root
Temperature Drift
50 PPM/
°
C from -40 to 75
°
C ambient
Decimal Point
User selectable decimal point
Minimum Span
Input 1 & Input 2: 0.40 mA
Calibration Range
An
Error
message will appear if input 1 and
input 2 signals are too close together.
Input
Range
4-20 mA
Minimum Span
Input 1 & Input 2
0.40 mA
Maximum
Voltage Drop &
Equivalent
Resistance
Without Backlight With Backlight
1.7 VDC @ 20 mA
4.7 VDC @ 20 mA
85
Ω @ 20 mA
235
Ω @ 20 mA
Loop-Powered
Backlight Option
Factory installed only. Powered directly
from the 4-20 mA loop, no batteries
required. Backlight can be enabled or
disabled via alternative wiring of terminal
block. The display brightness will increase
as the input signal current increases.
Input
Overload
Over current protection to 2 A max.
HART
Transparency
The meter does not interfere with existing
HART communications; it displays the 4-20
mA primary variable and it allows the HART
communications to pass through without
interruption.
The meter is not affected if a HART
communicator is connected to the loop.
The meter does not display secondary
HART variables.
Electromagnetic Compatibility
Emissions
EN 61326:2013
Safety requirements for measurement,
control, and laboratory use – Industrial
Group 1 Class A ISM emissions
requirements
Radiated
Emissions
Class A
Immunity
EN 61326:2013
Safety requirements for measurement,
control, and laboratory use
ESD
±4 kV contact,
±8 kV air
RFI – Amplitude
Modulated
80-1000 MHz @ 10 V/m,
1.4-2.0 GHz @ 3 V/m,
2.0-2.7 GHz @ 1 V/m,
80% AM (1 kHz)
EFT
±2 kV DC mains, ±1 kV other
Telco Surge
±1 kV
CRFI
3 V, 0.15-80 MHz,
1 kHz 80% AM