Instruction Manual
13
Reset Meter to Factory Defaults
When the parameters have been changed in a way
that is difficult to determine what’s happening, it might
be better to start the setup process from the factory
defaults.
Instructions to load factory defaults:
Enter the
Advanced
features menu.
See
Press
Up
arrow button to display
info
menu.
Press
Right
arrow button when
info
is shown.
Press
Enter
button when
rSt
is shown.
Press
Enter
again when display flashes
rSt
.
Note: If
Enter
is not pressed a second time within
three seconds,
rSt
will stop flashing and the last
Enter
press cancelled.
The meter goes through an initialization sequence
(same as on power-up) and loads the factory default
settings.
Factory Defaults & User
Settings
The following table shows the factory setting for most
of the programmable parameters on the meter. Next
to the factory setting, the user may record the new
setting for the particular application.
Model: _____________________________
S/N:
_____________________________
Date: _____________________________
Parameter
Display
Default
Setting
User
Setting
Decimal point
Dd.dd
2 places
Scale
SCL
Number of
Points
NPT
2
Input 1
in1
4.00 mA
Display 1
D1
4.00
Input 2
in2
20.00 mA
Display 2
D2
20.00
Advanced Features
Input
Conditioning
Function
Fnc
Linear
Filter
FIL
Off