PD2-6400
Helios High Voltage & Current Meter
www.predig.com
21
SPECIFICATIONS
Except where noted all specifications apply to operation at +25°C.
General
Display:
Two lines with 1.8" (46 mm) high digits, red LEDs; 6 digits
per line (-99999 to 999999), with lead zero blanking
Display Intensity:
Eight user-selectable intensity levels
Display Update Rate:
5/second (200 ms)
Overrange:
Display flashes
999999
Underrange:
Display flashes
-99999
Display Assignment:
Displays lines 1 & 2 may be assigned to
process values for Channels A (Ch-A, current), V (Ch-V, voltage),
or P (Ch-P, apparent power); toggle between (Ch-A & Ch-V, Ch-A &
Ch-P, Ch-V & Ch-P, and Ch-A, Ch-V, & Ch-P); relay set points; max
and/or min values for CH-A, Ch-V, or Ch-P; CH-A and units; Ch-V
and units; Ch-P and units; or Modbus input. The lower display may
also be set to show engineering units or be off, with no display.
Noise filter:
Programmable from 2 to 199 (0 will disable filter)
Filter Bypass:
Programmable from 0.1 to 99.9% of calibrated span
Recalibration:
All ranges are calibrated at the factory.
Recalibration is recommended at least every 12 months.
Max/Min Display:
Max/min readings reached by the process are
stored until reset by the user or until power to the meter is turned off.
Password:
Three programmable passwords restrict modification of
programmed settings.
Pass 1:
Allows use of function keys and digital inputs
Pass 2:
Allows use of function keys, digital inputs and editing set/
reset points
Pass 3:
Restricts all programming, function keys, and digital inputs
Non-Volatile Memory:
All programmed settings are stored in non-
volatile memory for a minimum of ten years if power is lost.
Power Options:
85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max or
12-24 VDC ±
10%, 15 W max. Powered over USB for configuration
only.
Fuse:
Required external fuse: UL Recognized, 5 A max, slow blow;
up to 6 meters may share one 5 A fuse.
Normal Mode Rejection:
Greater than 60 dB at 50/60 Hz
Isolation:
500 V AC/DC potential allowed between voltage and
current input channels. Channels isolated by 3 MΩ impedance
4 kV input/output-to-power line 500 V input-to-output or output-
to-P+ supply.
Overvoltage Category:
Installation Overvoltage Category II:
Local level with smaller transient overvoltages than Installation
Overvoltage Category III.
Environmental:
Operating temperature range:
-40 to 150°F (-40 to 65°C)
Storage temperature range:
-40 to 185°F (-40 to 85°C)
Relative humidity:
0 to 90% non-condensing
Connections:
Removable and integrated screw terminal blocks
accept 12 to 22 AWG wire.
Enclosure:
UL Type 4X,
IP65 rated. Polycarbonate & glass
blended plastic case, color: gray. Includes four PG11 through-hole
conduit openings, with two factory installed PG11, IP68, black nylon
threaded hole plugs with backing nuts.
Wall Mounting:
Four (4) mounting holes provided for mounting meter
to wall.
Pipe Mounting:
Optional pipe mounting kit (PDA6260) allows
for pipe mounting. Sold separately. See manual for mounting
instructions.
Tightening Torque:
Removable Screw Terminals:
5 lb-in (0.56 Nm)
Digital I/O and RS485 Terminals:
2.2 lb-in (0.25 Nm)
Overall Dimensions:
10.63
" x 12.59" x 4.77"
(270 mm x 319.7 mm x 121.2 mm) (W x H x D)
Weight:
6.10 lbs (2.76 kg)
UL File Number:
UL & C-UL Listed. E160849; 508 Industrial
Control Equipment.
Warranty:
3 years parts & labor
USB Connection:
Compatibility:
USB 2.0 Standard, Compliant
Connector Type:
Micro-B receptacle
Cable:
USB A Male to Micro-B Cable
Driver:
Microsoft
®
Windows
®
XP/Vista/7/8/10
Power:
USB Port
Voltage and Current Inputs
High Voltage Input:
One high voltage input (Channel V) 0-300 VDC
or VAC; Switch Selectable, Modbus PV (Slave)
High Current Input:
One high current input (Channel A)
0-5 AAC or ADC; Switch Selectable, Modbus PV (Slave)
Channels:
Channel A, Channel V, Channel P (Math Channel for
Apparent Power)
AC/DC Selection:
Switch selectable for AC or DC inputs. Channels
A and V share AC/DC selection.
Apparent Power Math:
Apparent power P calculated as P = A * V
Programmable Constants:
Constant C (Adder): -99.999 to
999.999, default: 0.000. Constant F (Factor): 0.001 to 999.999,
default: 1.000.
Accuracy:
ADC: 0.03% Full Scale ±1 count,
AAC: 0.1% Full Scale ±1 count,
VDC: 0.05% Full Scale ±1 count,
VAC: 0.15% Full Scale ±1 count, square root & programmable
exponent accuracy range: 10-100% of calibrated span
Temperature Drift:
0.005% of calibrated span/°C max from -40 to
65°C ambient
Signal Input Conditioning:
Linear, square root, programmable
exponent, or round horizontal tank volume calculation.
Multi-Point Linearization:
2 to 32 points for Channel A and V
Low-Flow Cutoff:
0-999999 (0 disables cutoff function).
Independent for Channel A and V.
Decimal Point:
Up to five decimal places or none:
d.ddddd
,
d.dddd
,
d.ddd
,
d.dd
,
d.d
, or
dddddd
Calibration Range:
Input
Channel
Input
Range
Minimum Span
Input 1 & Input 2
A
+/- 0-5 ADC/0-5 AAC
+/- 0.005 ADC/0.010 AAC
V
+/- 0-300 VDC/0-300 VAC +/- 0.1 VDC/0.3
Note: An error message will appear if the input 1 and input 2 signals
are too close together.
Input Impedance:
Voltage Input: greater than 3 MΩ.
Current Input: 0.01 Ω.
Input Overload:
Voltage input protected up to 500 VDC
Current input protected up to 10 A by a 10A/300V fast acting non-
resettable fuse. Fuse is NOT resettable after a fault; unit must be
factory reconditioned.
F4 Digital Input Contacts:
3.3 VDC on contact. Connect normally
open contacts across F4 to COM.
F4 Digital Input Logic Levels:
Logic High:
3 to 5 VDC
Logic Low:
0 to 1.25 VDC