PD301 - PD306 Smart Temp Transmitters
Instruction Manual
35
TROUBLESHOOTING
If the Smart Temperature Transmitter is not working as expected,
refer to the recommendations below.
Symptom Check/Action
No communication
•
Voltage too low
•
Check loop impedance
Fault or alarm current
(
≤
3.6 mA or
≥
22.0 mA)
•
Defective or open sensor
•
Incorrect programmed range
4-20 mA output is not correct
•
Check voltage across
transmitter
•
Reduce loop impedance
Output is fixed at 4 mA
•
Transmitter configured for
multi-drop mode
•
Change HART address to zero
Temperature reading is not
correct
•
Wrong or defective sensor
•
Check
scaling
•
Check offset value
Other symptoms not
described above
•
Call Technical Support for
assistance.