GSW
•
After approximately 2-3 minutes of operation,
check the frequency and voltage values; when they
are stable, the main circuit breaker of the socket kit
(where present) can be set to ON.
•
Set the main switch (
CP.1
) to ON.
•
Check that the generated voltage, frequency and
current values are suitable for the connected utilities.
“Manual panel with digital board” manual
start:
•
Make sure that the emergency button (
CP.2
) is
not pressed.
•
Set the main switch (
CP.1
) and main circuit
breaker of the socket kit (where present) to OFF.
•
Insert the key in the key block.
•
Turn the key clockwise until the 1st click ("ON"
position). This powers the board and the control
panel.
•
Turn the key clockwise until another click
("START" position), holding it manually until the
generator starts.
•
When you release the key it returns automatically
to "ON".
•
If the generator does not start up, make sure you
have carried out all the required operations before
starting and check whether any indicator light
signalling faults is on. If a fault is present, correct it
and try to restart by pressing the start button.
•
Leave the generator run until it reaches ideal
operating conditions (do not connect electric loads).
•
Check the engine to make sure that there is no
water, oil or fuel leakage.
•
Make sure that the air intake valves of the
alternator are not obstructed and that air can
circulate freely around the radiator.
•
After approximately 2-3 minutes of operation,
check the frequency and voltage values; when they
are stable, the main circuit breaker of the socket kit
(where present) can be set to ON.
•
Set the main switch (
CP.1
) to ON.
•
Check that the generated voltage, frequency and
current values are suitable for the connected utilities.
“Automatic panel with standard electronic
board” automatic starting:
•
Make sure that the emergency button (
CP.2
) is
not pressed.
•
Set the main switch (
CP.1
) and main circuit
breaker of the socket kit (where present) to ON.
•
Select the
“AUTO”
operating mode on the
electronic control board. The generator will start
automatically when it detects a power failure.
•
Refer to the supplied manual of the standard
electronic control board.
“Automatic panel with standard electronic
board” test mode starting:
•
Follow the guidelines to start in manual mode
“MAN”
, however, select the
“TEST”
mode on the
control board.
WARNING
To check the proper operating
conditions, it is recommended to
start the generator at least once
every 15 days without an electric
load connected and once a month
applying an electric load that is
50% of the rated power for about 30
minutes.
5.6
Stopping the generator
•
Set the main switch (
CP.1
) to OFF. Leave the
engine running for approximately 2-3 minutes to
allow it to cool off.
•
In the case of
“Automatic panel with standard
electronic board”
: follow the stopping instructions
provided in the supplied manual of the electronic
board.
NOTE:
The
“OFF”
mode can be selected on the
standard electronic control board to maintain the
stop condition and prevent the generator from being
started.
•
In the case of
“Manual panel with digital
board”
: turn the key selector (
CP.3
) to “OFF” and
wait for the engine to stop completely.
WARNING
It is FORBIDDEN to disconnect
loads from sockets that are 63A or
greater before having completely
switched the generator off.
88