4
Version No. V3R0
Safety Manual
9203 Solenoid / Alarm Driver
4.4 Safe parameterisation
The user is responsible for verifying the correctness of the configuration
parameters. (See section 14 Safe parameterisation - user responsibility).
Manual override may not be used for safety applications.
4.5 installation in hazardous areas
The IECex Installation drawing, ATEX Installation drawing and FM
Installation drawing shall be followed if the products are installed in
hazardous areas.
5. functional specification of the safety functions
Ex driver for the control of ON / OFF solenoids, acou stic alarms and LEDs
mounted in the hazardous area.
6. functional specification of the non-safety functions
The status relay (terminal 33 and 34), error signal on power rail (terminal 91)
and LED outputs are not suitable for use in any Safety Instrumented Function.
7. Safety parameters
Note
1
: The 9203 contains no lifetime limiting components, therefore the PFH
figures are valid for up to 12 years, according to IEC 61508.
B1A, B1B
B2A
Probability of dangerous Failure per Hour (PFH)
4.30E-08
4.60E-08
Note
1
Probability of failure on demand (PFD) -
1 year proof test interval
2.73E-04
2.92E-04
Proof test interval (10% of loop PFD)
5 years
4 years
Safe Failure Fraction
91%
91%
Demand response time
<10
ms
Demand mode
High
Demand rate
1000 s
Mean Time To Repair (MTTR)
24 hours
Diagnostic test interval
10 seconds
Hardware Fault Tolerance (HFT)
0
Component Type
B
SIL capability
SIL 2
Description of the “Safe State”
De-energised