9203 - Product Version 9203-001
23
9203QI01
Revision date:
2009-12-10
Version Revision
V3 R0
Prepared by:
PB
Page:
2/2
Uo
28 V
IIC
80 nF
4.2 mH
54 μH/Ω
Uo
28 V
IIC
80 nF
2.69 mH 44 μH/Ω
Io
93 mA
IIB
640 nF
16.8 mH 218 μH/Ω
Io
115 mA
IIB
640 nF
10.8 mH 176 μH/Ω
Po
0.65 W
IIA
2.1 μF
32.6 mH 436 μH/Ω
Po
0.81 W
IIA
2.1 μF
20.8 mH 353 μH/Ω
Uo
28 V
IIC
80 nF
3.5 mH
50 μH/Ω
Uo
28 V
IIC
Io
100 mA
IIB
640 nF
14.2 mH 201 μH/Ω
Io
125 mA
IIB
640 nF
9.1 mH 162 μH/Ω
Po
0.70 W
IIA
2.1 μF
27.6 mH 402 μH/Ω
Po
0.88 W
IIA
2.1 μF
17.6 mH 325 μH/Ω
Uo
28 V
IIC
80 nF
2.9 mH
46 μH/Ω
Uo
28 V
IIC
Io
110 mA
IIB
640 nF
11.8 mH 184 μH/Ω
Io
135 mA
IIB
640 nF
7.8 mH 150 μH/Ω
Po
0.77 W
IIA
2.1 μF
22.8 mH 369 μH/Ω
Po
0.95 W
IIA
2.1 μF
15.1 mH 301 μH/Ω
Modul 9203B2A
Terminal 41-44
Co
Lo
Lo/Ro
Modul 9203B2A
Terminal 41-43
Co
Lo
Lo/Ro
Modul 9203B2A
Terminal 41-42
Co
Lo
Lo/Ro
Modul 9203B1A & 9203B1B
Terminal 41-44 / 51-54
Co
Lo
Lo/Ro
Modul 9203B1A & 9203B1B
Terminal 41-43 / 51-53
Co
Lo
Lo/Ro
Modul 9203B1A & 9203B1B
Terminal 41-42 / 51-52
Co
Lo
Lo/Ro
Terminal (31,32)
Terminal (11,12 and 13,14)
Supply:
Input:
Voltage
19.2 – 31.2 VDC
Voltage
max. 28 VDC
Power max.
3.5 W
Trig: NPN
Low < 2 V, High > 4 V
Trig: PNP
Low < 8 V, High > 10 V
Terminal (33,34)
Status Relay:
Non Hazardous location
Zone 2 installation
Voltage max.
125 VAC / 110 VDC
32 VAC / 32 VDC
Power max.
62.5 VA / 32 W
16 VA / 32 W
Current max.
0.5 AAC / 0.3 ADC
0.5 AAC / 1 ADC
Installation notes.
For installation in Zone 2, the module must be installed in an outer enclosure having an IP protection
of at least IP54 according to type of protection Ex-n or Ex-e.
For installation on Power Rail in Zone 2, only Power Rail type 9400 supplied by Power Control Unit
type 9410 is allowed.
In type of protection “intrinsic safety iD” the parameters for intrinsic safety for gas group IIB are
applicable.
If the sensor circuits (Terminals 41...44, 51…54) have been installed in a type of protection other than
“intrinsic safety”, the module shall not be re-installed in type of protection ”intrinsic safety”.
Do not separate connectors when energized and an explosive gas mixture is present.
Do not mount or remove modules from the Power Rail when an explosive gas mixture is present.
The maximum internal Power dissipation for adjacent modules is assumed to be max. 2 W each.