9203 - Product Version 9203-001
27
9203QF01
LERBAKKEN 10, 8410 RØNDE DENMARK
Revision date:
2009-12-10
Version Revision
V3 R0
Prepared by:
PB
Page:
2/2
Uo/Voc
28 V
IIC or A,B
80 nF
4.2 mH
54
μ
H/
Ω
Uo/Voc
28 V
IIC or A,B
80 nF
2.69 mH 44
μ
H/
Ω
Io/Isc
93 mA
IIB or C,E,F
640 nF
16.8 mH 218
μ
H/
Ω
Io/Isc
115 mA
IIB or C,E,F
640 nF
10.8 mH 176
μ
H/
Ω
Po
0.65 W
IIA or D,G
2.1
μ
F
32.6 mH 436
μ
H/
Ω
Po
0.81 W
IIA or D,G
2.1
μ
F
20.8 mH 353
μ
H/
Ω
Uo/Voc
28 V
IIC or A,B
80 nF
3.5 mH
50
μ
H/
Ω
Uo/Voc
28 V
IIC or A,B
Io/Isc
100 mA
IIB or C,E,F
640 nF
14.2 mH 201
μ
H/
Ω
Io/Isc
125 mA
IIB or C,E,F
640 nF
9.1 mH 162
μ
H/
Ω
Po
0.70 W
IIA or D,G
2.1
μ
F
27.6 mH 402
μ
H/
Ω
Po
0.88 W
IIA or D,G
2.1
μ
F
17.6 mH 325
μ
H/
Ω
Uo/Voc
28 V
IIC or A,B
80 nF
2.9 mH
46
μ
H/
Ω
Uo/Voc
28 V
IIC or A,B
Io/Isc
110 mA
IIB or C,E,F
640 nF
11.8 mH 184
μ
H/
Ω
Io/Isc
135 mA
IIB or C,E,F
640 nF
7.8 mH 150
μ
H/
Ω
Po
0.77 W
IIA or D,G
2.1
μ
F
22.8 mH 369
μ
H/
Ω
Po
0.95 W
IIA or D,G
2.1
μ
F
15.1 mH 301
μ
H/
Ω
Modul 9203B1A & 9203B1B
Terminal 41-42 / 51-52
Co/Ca
Lo/La
Lo/Ro or
La/Ra
Modul 9203B2A
Terminal 41-42
Co/Ca
Lo/La
Lo/Ro or
La/Ra
Modul 9203B1A & 9203B1B
Terminal 41-43 / 51-53
Co/Ca
Lo/La
Lo/Ro or
La/Ra
Modul 9203B2A
Terminal 41-43
Co/Ca
Lo/La
Lo/Ro or
La/Ra
Modul 9203B1A & 9203B1B
Terminal 41-44 / 51-54
Co/Ca
Lo/La
Lo/Ro or
La/Ra
Modul 9203B2A
Terminal 41-44
Co/Ca
Lo/La
Lo/Ro or
La/Ra
Terminal (31,32)
Terminal (11,12 and 13,14)
Supply:
Input:
Voltage
19.2 – 31.2 VDC
Voltage
max. 28 VDC
Power max.
3.5 W
Trig: NPN
Low < 2 V, High > 4 V
Trig: PNP
Low < 8 V, High > 10 V
Terminal (33,34)
Status Relay:
Non Hazardous location: Division 2 or Zone 2 installation:
Voltage max.
125 VAC / 110 VDC
32 VAC / 32 VDC
Power max.
62.5 VA / 32 W
16 VA / 32 W
Current max.
0.5 AAC / 0.3 ADC
0.5 AAC / 1 ADC
Installation notes:
The installation and wiring shall be in accordance with the Canadian Electrical Code for Canada and
National Electrical Code NFPA 70, Article 500 or 505 for installation in USA.
The module must be supplied from a Power Supply having double or reinforced insulation.
The use of stranded wires is not permitted for mains wiring except when wires are fitted with cable
ends.
For installation on the 9400 Power Rail the power must be supplied from Power Control Module Unit
9410.
The module must be installed in pollution degree 2 or better.
The module must be installed in an enclosure suitable for the environment for which it is used.
For installation in Zone 2 or Division 2, the module must be installed in a suitable outer enclosure
according to the regulations in the CEC for Canada or NEC for USA.
The module is galvanically isolated and does not require grounding.
Use 60 / 75 ºC copper conductors with wire size AWG: (26-14).
The maximum internal Power dissipation for adjacent modules is assumed to be max. 2 W each.
Warning:
Substitution of components may impair intrinsic safety and / or suitability for Div. 2 / Zone 2.
Warning:
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
Warning:
Do not mount or remove modules from the Power Rail when an explosive gas mixture is
present.