24
6337V100-IN
6335QI01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
Revision date:
2011-02-01
Version Revision
V3R0
0Page:
1/2
IECEx Installation drawing
For safe installation of 6335D, 6336D or 6337D the following must be observed. The module shall
only be installed by qualified personnel who are familiar with the national and international laws,
directives and standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
IECEx Certificate IECEx KEM.10.0084X
Marking
Standards:
IEC60079-11:2006, IEC60079-0: 2007,
IEC60079-26:2006, IEC61241-11:2005
Non Hazardous Area
Hazardous area
Zone 0, 1, 2, 20, 21, 22
Ex ia IIC T6..T5 Ga
Ex ia IIIC Da
Terminal:
41,42,43,44
Uo: 9.6 VDC
Io: 28 mA
Po: 67 mW
Lo: 35 mH
Co: 3.5
μ
F
Terminal:
11,12,13,14 and
21,22,23,24
Ui: 30 VDC
Ii: 120 mA
Pi: 0.84 W
Li: 10
μ
H
Ci: 2.0nF
Terminal:
51,52,53,54
Uo: 9.6 VDC
Io: 28 mA
Po: 67 mW
Lo: 35 mH
Co: 3.5
μ
F
13
12
44
43
42
41
+
-
Barrier
23
22
54
53
52
51
+
-
Barrier
6335D
6336D
6337D
CH2
CH1
21
24
14
11
Ex HART
Communicator
R
R
250 < R < 1100 ohm
T5: -40
≤
Ta
≤
60ºC
T6: -40
≤
Ta
≤
40ºC