6335QC02
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
Revision date:
2011-03-10
Version Revision
V3R0
Page:
1/1
CSA Installation drawing
Installation notes.
The Transmitter must be installed in a suitable enclosure to meet installation codes stipulated in The
Canadian Electrical Code (CEC).
Channel 1 and Channel 2 are separate channels and therefore separate shielded cables
shall be used for each channel.
Substitution of components may impair intrinsic safety.
Non Hazardous Location
Hazardous (Classified ) Location
Class I, Division 1, Group A,B,C,D
Class I, Zone 0, IIC
Terminal:
41,42,43,44
Uo: 9.6 VDC
Io: 28 mA
Po: 67 mW
Lo: 35 mH
Co: 3.5
μ
F
Terminal:
11,12,13,14 and
21,22,23,24
Ui: 30 VDC
Ii: 120 mA
Pi: 0.84 W
Li: 10
μ
H
Ci: 2.0nF
Co(Ca)
>
∑
(Ci+Ccable)
Lo(La)
>
∑
(Li+Lcable)
T6: -40
≤
Ta
≤
60ºC
Terminal:
51,52,53,54
Uo: 9.6 VDC
Io: 28 mA
Po: 67 mW
Lo: 35 mH
Co: 3.5
μ
F
13
12
44
43
42
41
+
-
Barrier
23
22
54
53
52
51
+
-
Barrier
6335D
6336D
6337D
CH2
CH1
21
24
14
11
Ex HART
Communicator
R
R
250 < R < 1100 ohm