background image

 

5300QF01

LERBAKKEN 10, 8410 RØNDE DENMARK.       WWW.PRELECTRONICS.COM

 

 

   

Revision date: 

2014-03-31 

                 Version Revision 

           V8R0 

Doc. No. 

5300Q502 Rev AH   

Page: 

1/2

 

 

FM Installation Drawing 5300Q502 Rev AH 

 

Model 5331C,5331D, 5333C, 5333D and 5343B 

 

 

 

 

 

 

 

Model 5335C, 5335D, 5336D, 5337D 

 

 

 

 

 

 

 

Non

 

Hazardous

 

Location

Hazardous

 

(Classified)

 

Location

Associated Apparatus

or Barrier  

with 

entity Parameters:

SENSOR

1

2

3

4

5

6

UM < 250V

Voc or Uo  < Vmax or Ui

Isc or Io   <   Imax or Ii

Po  <  Pi

Ca or Co > Ci + Ccable

La or Lo  > Li + Lcable

This

 

device

 

must

 

not

 

be

 

connected

 

to

 

any

 

associated

 

apparatus

 

which

 

uses

 

or

 

generates

 

more

 

than

 

250

 

VRMS

+

Terminal 1 , 2

Vmax or Ui: 30 V

Imax or Ii: 120 mA

Pmax or Pi: 0.84 W

Ci: 1 nF

Li:10 uH

Terminal 3,4,5,6

Vt or Uo: 9.6 V

It or Io: 28 mA

Pt or Po: 67.2 mW

Ca or Co: 3.5 uF

La or Lo: 35 mH

Ambient

 

temperature

 

limits

T4:

 ‐

40

 

to

 

+

 

85

 

deg.

 

Celcius

T6:

 ‐

40

 

to

 

+

 

60

 

deg.

 

Celcius

Class I,Division1, Groups, A,B,C,D T4..T6

Class I, Zone 0, AEx ia  IIC T4..T6

Non

 

Hazardous

 

Location

Hazardous

 

(Classified)

 

Location

Associated Apparatus

or Barrier  

with 

entity Parameters:

SENSOR

1

2

3

4

5

6

UM < 250V

Voc or Uo  < Vmax or Ui

Isc or Io   <   Imax or Ii

Po  <  Pi

Ca or Co > Ci + Ccable

La or Lo  > Li + Lcable

This

 

device

 

must

 

not

 

be

 

connected

 

to

 

any

 

associated

 

apparatus

 

which

 

uses

 

or

 

generates

 

more

 

than

 

250

 

VRMS

+

Terminal 1 , 2

Vmax or Ui: 30 V

Imax or Ii: 120 mA

Pmax or Pi: 0.84 W

Ci: 1 nF

Li:10 uH

Terminal 3,4,5,6

Vt or Uo: 9.6 V

It or Io: 28 mA

Pt or Po: 67.2 mW

Ca or Co: 3.5 uF

La or Lo: 35 mH

Ambient

 

temperature

 

limits

T4:

 ‐

40

 

to

 

+

 

85

 

deg.

 

Celcius

T6:

 ‐

40

 

to

 

+

 

60

 

deg.

 

Celcius

Class I,Division1, Groups, A,B,C,D T4..T6

Class I, Zone 0, AEx ia IIC T4..T6

5331V114-UK

 19

Summary of Contents for 5331A

Page 1: ...5 3 3 1 2 W i r e P r o g r a m m a b l e T r a n s m i t t e r N o 5 3 3 1 V 1 1 4 U K F r o m s e r n o 1 4 1 3 6 5 0 0 1 ...

Page 2: ...Notes The following list provides notes concerning revisions of this document Rev ID Date Notes 113 13 45 IECEx and INMETRO approvals added 114 15 10 PESO CCOE approval added GOST approval replaced with EAC approval ...

Page 3: ...s 8 Block diagram 9 Programming 10 Mechanical specifications 11 Mounting of sensor wires 11 Appendix 12 ATEX Installation Drawing 5331A 13 ATEX Installation Drawing 5331D 14 IECEx Installation Drawing 5331A 16 IECEx Installation Drawing 5331D 17 FM Installation Drawing 5331D 19 CSA Installation Drawing 5331D 21 INMETRO Instruções de Segurança 5331A 22 INMETRO Instruções de Segurança 5331D 23 ...

Page 4: ...current signal for instance from valves or Ohmic level sensors Amplification of a bipolar mV signal to a standard 4 20 mA current signal Technical characteristics Within a few seconds the user can program PR5331 to measure temperatures within all ranges defined by the norms The RTD and resistance inputs have cable compensation for 2 3 and 4 wire connection Continuous check of vital stored data for...

Page 5: ...V mA V mA V mA V mA RTD to 4 20 mA TC to 4 20 mA Resistance to 4 20 mA mV to 4 20 mA 2 wire installation in control room 2 wire installation in control room 2 wire installation in control room 2 wire installation in control room ...

Page 6: ...Communications interface Loop Link Signal noise ratio min 60 dB Response time programmable 1 60 s EEprom error check 3 5 s Signal dynamics input 20 bit Signal dynamics output 16 bit Calibration temperature 20 28 C Accuracy the greater of general and basic values Order 5331 Type Version Ambient temperature Galvanic isolation 5331 Standard A CSA FM ATEX IECEx INMETRO D 40 C 85 C 3 1500 VAC B General...

Page 7: ...0 of selec max value Cable resistance per wire max 5 Ω Sensor current nom 0 2 mA Effect of sensor cable resistance 3 4 wire 0 002 Ω Ω Sensor error detection Yes Basic values Input type Basic accuracy Temperature coefficient RTD 0 2 C 0 01 C C Lin R 0 1 Ω 10 mW C Volt 10 µV 1 µV C TC type E J K L N T U 1 C 0 05 C C TC type B R S W3 W5 LR 2 C 0 2 C C EMC immunity influence 0 5 of span Extended EMC i...

Page 8: ...ce Vsupply 7 2 0 023 Ω Load stability 0 01 of span 100 Ω Sensor error detection Programmable 3 5 23 mA Namur NE43 Upscale 23 mA Namur NE43 Downscale 3 5 mA Of span Of the presently selected range Type Min temperature Max temperature Min span Standard B E J K L N R S T U W3 W5 LR 400 C 100 C 100 C 180 C 100 C 180 C 50 C 50 C 200 C 200 C 0 C 0 C 200 C 1820 C 1000 C 1200 C 1372 C 900 C 1300 C 1760 C ...

Page 9: ...26 1 Marine approval Det Norske Veritas Ships Offshore Stand f Certific No 2 4 Ex I S ATEX 94 9 EC 5331A KEMA 10ATEX0002 X 5331D KEMA 06ATEX0062 X FM certificate 2D5A7 CSA certificate 1125003 IECEx DEK 13 0035X INMETRO DEKRA 13 0001 X CCOE P337392 2 EAC Ex TR CU 012 2011 RU C DK GB08 V 00410 ...

Page 10: ... mA 3 4 6 5 3 4 6 5 3 4 6 5 3 4 6 5 3 4 6 5 3 4 6 5 3 4 6 5 3 4 6 5 3 4 6 5 Output 2 wire installation Input Resistance 2 wire Resistance 3 wire Resistance 4 wire RTD 2 wire RTD 3 wire RTD 4 wire TC internal CJC TC external CJC mV ...

Page 11: ...14 UK 9 Block diagram 0 16 m A 4 3 2 1 5 6 4 3 2 m V mA M UX 4 m A 5331 PGA D A C om m A D C PU E E PRO M Input gnd Supply 4 20 mA TC Ext CJC mV RTD lin R wire Int CJC Ex circuit only 5331D Supply 7 2 35 VDC ...

Page 12: ... areas Order Loop Link 5331 1 2 Loop Link 5909 USB File Product Input Output C ommunication Language Option 08 30 00 PRetop 5331 Date 2004 8 10 043201594 PRelectronics Analog input Analog output Serial no Inputtype Outputtype 4 20mA Upscale Sensor error Pt100 DIN IEC 0 00 50 00C 3 wire 1 00sec Inputrange Connection Cold junction comp Response time Tag no Disconnect Vsupply Connectedonlyfor on line...

Page 13: ...20 2 mm ø 6 mm 33 mm ø 44 mm 5331V114 UK 11 Mechanical specifications Mounting of sensor wires Wires must be mounted between the metal plates ...

Page 14: ...X Installation Drawing 5331D IECEx installation drawing 5331A IECEx installation drawing 5331D FM Installation Drawing 5331D CSA Installation Drawing 5331D INMETRO Instruções de Segurança 5331A INMETRO Instruções de Segurança 5331D 12 5331V114 UK ...

Page 15: ...fe use For type of protection Ex nA the transmitter shall be mounted in a metal enclosure providing a degree of protection of at least IP54 according to EN60529 For use in the presence of combustible dusts the transmitter shall be mounted in an enclosure providing a degree of protection of at least IP6X in accordance with EN60529 the surface temperature of the outer enclosure is 20 K above the amb...

Page 16: ...ectives and standards that apply to this area Year of manufacture can be taken from the first two digits in the serial number ATEX Certificate KEMA 06ATEX 0062 X Marking Standards EN 60079 0 2012 EN 60079 11 2012 EN 60079 26 2007 EN 60079 15 2010 Non Hazardous Area Hazardous area Zone 0 1 2 20 21 22 II 1 G Ex ia IIC T4 T6 Ga II 1 D Ex ia IIIC Da II 1 M Ex ia I Ma 1 2 6 5 4 3 Barrier 5331D 5334B Te...

Page 17: ...num if must be installed such that ignition sources due to impact and friction sparks are excluded if the enclosure is made of non metallic materials electrostatic charging shall be avoided For installation in a potentially explosive dust atmosphere the following instructions apply The transmitter shall be mounted in a metal enclosure form B according to DIN43729 that is providing a degree of prot...

Page 18: ...llation the transmitter must be installed in enclosure providing a degree of protection of at least IP20 according to IEC60529 and that is suitable for the application Cable entry devices and blanking elements shall fulfill the same requirements For an ambient temperature 60ºC heat resistant cables shall be used with a rating of at least 20 K above the ambient temperature For installation in a pot...

Page 19: ...ives and standards that apply to this area Year of manufacture can be taken from the first two digits in the serial number Certificate IECEx DEK 13 0035X Marking Standards IEC 60079 0 2011 IEC 60079 11 2011 IEC 60079 26 2006 Non Hazardous Area Hazardous area Zone 0 1 2 20 21 22 M1 Ex ia IIC T4 T6 Ga Ex ia IIIC Da Ex ia I Ma 1 2 6 5 4 3 Barrier 5331D 5334B Terminal 3 4 5 6 Uo 9 6 VDC Io 25 mA Po 60...

Page 20: ...quiring the use of equipment protection level Ga Ma and Mb and if the enclosure is made of aluminum it must be installed such that ignition sources due to impact and friction sparks are excluded For installation in a potentially explosive dust atmosphere the following instructions apply For explosive dust atmospheres the surface temperature of the outer enclosure is 20 K above the ambient temperat...

Page 21: ...r Uo 9 6 V It or Io 28 mA Pt or Po 67 2 mW Ca or Co 3 5 uF La or Lo 35 mH Ambient temperature limits T4 40 to 85 deg Celcius T6 40 to 60 deg Celcius Class I Division1 Groups A B C D T4 T6 Class I Zone 0 AEx ia IIC T4 T6 Non Hazardous Location Hazardous Classified Location Associated Apparatus or Barrier with entity Parameters SENSOR 1 2 3 4 5 6 UM 250V Voc or Uo Vmax or Ui Isc or Io Imax or Ii Po ...

Page 22: ...hich the device can receive and remain intrinsically safe must be equal to or greater than the voltage Uo or VOC or Vt and current Io or ISC or It and the power Po which can be delivered by the barrier The sum of the maximum unprotected capacitance Ci for each intrinsically device and the interconnect ing wiring must be less than the capacitance Ca which can be safely connected to the barrier The ...

Page 23: ...C and D Class I Zone 0 AEx ia IIC Ga Warning Substitution of components may impair intrinsic safety The transmitters must be installed in a suitable enclosure to meet installation codes stipulated in the Canadian Electrical Code CEC or for US the National Electrical Code NEC Non Hazardous Area Hazardous area 1 2 6 5 4 3 Barrier Module 5335D 5336D and 5337D Terminal 3 4 5 6 Uo 9 6 VDC Io 28 mA Po 6...

Page 24: ...sor deve ser instalado em um invólucro proporcionando um grau de proteção de IP20 pelo menos de acordo com a norma IEC60529 que é adequado para a aplicação Dispositivos de entrada de cabos e elementos de supressão devem cumprir os mesmos requisitos Para uma temperatura ambiente 60 º C os cabos resistentes ao calor precisam ser utilizados com uma classificação de pelo menos 20 K acima da temperatur...

Page 25: ...drões que se aplicam a esta área Ano de fabricação pode ser pego dos dois primeiros dígitos do número de série Certificado DEKRA 13 0001 X Indicação Padrões ABNT NBR IEC 60079 0 2008 ABNT NBR IEC 60079 11 2009 IEC 60079 15 2010 ABNT NBR IEC 60079 26 2008 Sem áreas perigosas Áreas Perigosas Zona 0 1 2 20 21 22 Ex ia IIC T6 T4 Ga Ex ia IIIC Da 1 2 6 5 4 3 Barrier 5331D 5334B Terminal 3 4 5 6 Uo 9 6 ...

Page 26: ...eve ser instalado de modo que mesmo em caso de avaria rara fontes de ignição devido a impacto e fricção faíscas são eliminadas se o enclosure é feito de materiais não metálicos cargas eletroestáticas devem ser evitadas Para instalação em atmosfera de poeira potencialmente explosiva as instruções a seguir O transmissor deve ser montado em enclosure de metal forma B de acordo com DIN43729 que está f...

Page 27: ...alvanic isolators for analog and digital signals as well as HART signals A wide product range with both loop powered and universal isolators featuring linearization inversion and scaling of output signals Isolation Interfaces for analog and digital signals as well as HART signals between sensors I P converters frequency signals and control systems in Ex zone 0 1 2 and for some devices in zone 20 2...

Page 28: ...m www prelectronics se sales se prelectronics com www prelectronics com sales uk prelectronics com www prelectronics com sales us prelectronics com www prelectronics cn sales cn prelectronics com www prelectronics be sales be prelectronics com Head office Denmark www prelectronics com PR electronics A S sales prelectronics dk Lerbakken 10 tel 45 86 37 26 77 DK 8410 Rønde fax 45 86 37 30 85 ...

Reviews: