background image

8 4590V101-UK

Adaptor Mode

   The 4590 is a handheld device that can operate as an adapter between the detachable 4501 Programming Display or the 

4511 Digital Communication Enabler and selected devices in the 3000 series. This allows for configuration and monitoring 
of process parameters of the connected devices.

  Note for connection to a 3000 series product, the PR USB-B to a 2.5 mm jack cable must be used. 

   By pressing the power button, the 4590 will power on, and show the status of the attached 3000 device on the 

4501/4511.

   If the 3000 device is powered, the 4501/4511 display will indicate the process variable or can be manually set to go into 

program mode.

  If the 3000 device is not powered the 4501/4511 display will be in program mode only.

   Indication of battery level is displayed via the LEDs.  This can be activated by using the Power/Wake-up button.  If while 

pressing the Power/Wake-up button the LEDs are off, or only one LED is lit, the batteries should be exchanged.  To extend 
battery life the 4590 will automatically detect if it is not in use, and will consequently shut itself down to conserve 
battery power.

  Battery life in Adaptor Mode is approximately 1 year of daily use, depending upon battery type.

Connection of ConfigMate 4590 to a PR 3000 Device

USB and PReset installation (Docking Mode Only)

The USB communication is supported by Windows Windows 7, 8 and 10. PR devices that can either be programmed or have 
their configurations saved, backedup/restored via ConfigMate 4590 are available in the configuration program PReset ver. 6.0 
or higher.

Technical characteristics

The PC program PReset ver. 6.0 or higher supports ConfigMate 4590. To conserve power on a laptop, the USB connector of the 
4590 can be connected to an externally supplied hub. The communications connector on the PR device is galvanically isolated 
from the USB connection on the PC.

System requirements

Access to internet is needed for installation of USB drivers
Installation rights
Windows 7, 8 or 10 with the following recommendations: 
 Processor   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .  > 1 GHz 
 Memory   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   1 GB RAM (32-bit) or 2 GB RAM (64-bit)
  Hard disk space  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   16 GB (32-bit) or 20 GB (64-bit)

Summary of Contents for 4590

Page 1: ...FORMANCE MADE SMARTER Product Manual 4590 ConfigMate USB communications interface TEMPERATURE I S INTERFACES COMMUNICATION INTERFACES MULTIFUNCTIONAL ISOLATION DISPLAY No 4590V101 UK From ser no 110404001 ...

Page 2: ...allows for local monitoring of process values device configuration error detection and signal simulation The next generation our 4511 Remote Operator Interface ROI does all that and more adding remote digital communications via Modbus RTU while the analog output signals are still available for redundancy With the 4511 you can further expand connectivity with a PR gateway which connects via industr...

Page 3: ...Mode 6 Connection of ConfigMate 4590 to a PC in Docking Mode 7 Connection of ConfigMate 4590 to a PR 4000 9000 Device 7 Adaptor Mode 8 Connection of ConfigMate 4590 to a PR 3000 Device 8 USB and PReset installation Docking Mode Only 8 Technical characteristics 8 System requirements 8 Installation of PReset 9 Configuration of USB communication in PReset 9 ...

Page 4: ...ng risk of explosion hazard To avoid risk of explosion and injury Do not use this equipment when a flammable or combustible atmosphere is present Do not replace batteries unless area is known to be safe Use 3 x 1 5 V TYPE AAA batteries only and insert correctly as stipulated in battery compartment Warning risk of electrical shock To avoid risk of electrical shock and injury Do not disconnect the c...

Page 5: ...eratures mechanical vibrations and shock and rain and heavy moisture Normal operation Only technicians who are familiar with the technical terms warnings and instructions in the manual and who are able to follow these should connect the device Should there be any doubt as to the correct handling of the device please contact your local distributor or alternatively PR electronics A S www prelectroni...

Page 6: ... note For connection to a PC the USB B to USB A cable must be used In docking station mode the 4590 will be powered from the PC s USB power source no batteries are required The 4501 4511 display will indicate USB line communication with a very short blink when uploading or downloading configurations from to the 4501 The selected 3000 4000 and 9000 device configurations can only be viewed in the Pr...

Page 7: ...rectly or via ConfigMate 4590 To upload a configuration from a 3000 4000 9000 device to the 4501 4511 you must manually go into the Memory Menu of the 4501 4511 and SAVE from the target device into the 4501 4511 To download a configuration to a 3000 4000 9000 device from the 4501 4511 you must manually go into the Memory Menu of the 4501 4511 and LOAD to the target device from the 4501 4511 For fu...

Page 8: ...d be exchanged To extend battery life the 4590 will automatically detect if it is not in use and will consequently shut itself down to conserve battery power Battery life in Adaptor Mode is approximately 1 year of daily use depending upon battery type Connection of ConfigMate 4590 to a PR 3000 Device USB and PReset installation Docking Mode Only The USB communication is supported by Windows Window...

Page 9: ...t software from www prelectronics com downloads software preset software Note that this is in the form of a zip file 2 Unzip the file to the desired location 3 To start the installation double click the setup exe file When the installation program has been started on screen guidelines will guide you through the rest of the installation The complete installation guide for PReset can be downloaded f...

Page 10: ...entation We are headquartered in Denmark and have offices and authorized partners the world over We are a local business with a global reach This means that we are always nearby and know your local markets well We are committed to your satisfaction and provide PERFORMANCE MADE SMARTER all around the world For more information on our warranty program or to meet with a sales representative in your r...

Page 11: ...andards for products communicating monitoring and connecting our customers process measurement points to their process control systems Our innovative patented technologies are derived from our extensive R D facilities and from having a great understanding of our customers needs and processes We are guided by principles of simplicity focus courage and excellence enabling some of the world s greates...

Reviews: