When the temperature under rated conditions exceeds 70°C at the cable or conduit entry point, or 80°C at the branching point
of the conductors, the temperature specification of the selected cable shall be in compliance with the actual measured
temperature.
Provisions shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40%.
For installation on power rail in Zone 2, only Power Rail type 9400 supplied by Power Control Unit type 9410 is allowed.
To prevent ignition of the explosive atmospheres, disconnect power before servicing and do not separate connectors when
energised and an explosive gas mixture is present.
Do not mount or remove devices from the power rail when an explosive gas mixture is present.
Cleaning
When disconnected, the device may be cleaned with a cloth moistened with distilled water.
Liability
To the extent the instructions in this manual are not strictly observed, the custom er cannot advance a demand against PR
electronics A/S that would otherwise exist according to the concluded sales agreement.