10
Parameter Description
Settings
(Default Value)
Cool ON Time
to 120.0 Seconds
(Default : 2.0)
0.1 to Value set for
Cool Pulse Time
(Default : 1.0)
0 to Power High
(Default : 0)
0.1 to Value set
for Pulse Time
(Default : 1.0)
1 to 999
(Default : 2)
HEAT POWER LOW
(Available for PID Control only)
Sets the lower % Output power limit for OP1.
(Available for Pulsed On-Off Control with bi-directional mode)
Sets the ON pulse time in Seconds for Relay/SSR Output for OP2.
*
COOL ON TIME
(Available for Pulsed On-Off Control with bi-directional mode)
Sets the total ‘On + Off’ pulse time in Seconds for Relay / SSR
Output for OP2.
*
COOL PULSE TIME
(Available for On-Off or Pulsed On-Off Control with bi-directional mode)
Sets differential (dead) band between On-Off switching for OP2.
*
COOL HYSTERESIS
ON TIME
(Available for Pulsed On-Off Control only)
Sets the ON pulse time in Seconds for Relay/SSR Output for OP1.
HEAT POWER HIGH
(Available for PID Control only)
Sets the higher % Output power limit for OP1 .
Power Low to 100
(Default : 100)
0 to Cool Power High
(Default : 0)
Cool Power Low to 100
(Default : 100)
(Available for PID Control with bi-directional, that is, Heat-Cool mode)
Sets the higher % Output power limit for OP2.
*
COOL POWER HIGH
(Available for PID Control with bi-directional, that is, Heat-Cool mode)
Sets the lower % Output power limit for OP2.
*
COOL POWER LOW
*
The parameters marked with
asterisk
symbol
are available only if the controller is supplied with Bi-Directional control (Heat +
Cool) mode option.
User Manual
EPSILON