COMMAND BOARD:
Check the label attached to the product
(according to the model on the side) which
is the board part of the operator. Once
this is done, consult the board manual
that is available for download at www.
ppa.com.br and make all connections and
configurations.
Lote:
Código:
Modelo:
Redução:
Tecnologia:
Voltagem:
Central:
Tamanho:
Montagem:
Carenagem:
Engrenagem:
MAINTENANCE
In the table below, we will mention some PROBLEMS - DEFECTS, PROBABLE CAUSES
AND CORRECTIONS - which may occur in the operator. Before any maintenance,
the total shutdown of the power grid is necessary.
DEFECTS
PROBABLE CAUSES
CORRECTIONS
Engine does not
start / does not
move
A) Power off
B) Open / burned fuse
C) Locked gate
D) Limit switch defective
A) Make sure the mains power is
turned on correctly
B) Replace fuse with the same
specification
C) Make sure that there are no
objects blocking the gate operation
D) Replace the limit switch system
(analog and / or digital)
Motor blocked
A) Inverted motor connection
B) Locked gate or trigger
A) Check the motor wires
B) Set to manual mode and check
separately
The board does
not accept
command
A) Fuse blown
B) Power off (power)
C) Defect on remote control
unloaded
D) Transmitter range (remote
control)
A) Replace the fuse
B) Connect the mains (power
supply)
C) Check and replace battery
D) Check the position of the
receiver's antenna and, if necessary,
reposition to ensure a reach
Motor only turns
to one side
A) Inverted motor wires
B) Inverted limit switch system
C) Defect in the command board
A) Check the motor connection
B) Invert the limit course connector
(analog and / or digital)
C) Replace the board