Installation
18
Powerware
®
9125 Two-in-One (5000/6000 VA) PDM User’s Guide
S
Rev B
www.powerware.com
Table 1. Plug-Receptacle PDM Input/Output Voltage Settings
PPDM L6-30, and PPDM L6-20 Models
Input Voltage
PDM Output Voltage
Input Voltage
(from UPS)
208V Switch Position
(HV/LV)
Default 240V Switch Position
(HV/LV)
208
208/120
208/104
220
220/126
220/110
230
230/131
230/115
240
240/136
240/120
PPDM L5-30 Models
Input Voltage
PDM Output Voltage
Input Voltage
(from UPS)
208V Switch Position
Default 240V Switch Position
208
120
104
220
126
110
230
131
115
240
136
120
PPDM L14-30 Models
Input Voltage
PDM Output Voltage
Input Voltage
(from UPS)
208V Switch Position
(L14-30R/5-15R)
Default 240V Switch Position
(L14-30R/5-15R)
208
240/120
208/104
220
252/126
220/110
230
262/131
230/115
240
272/136
240/120
PPDM L6-30&L14-30 Models
Input Voltage
PDM Output Voltage
Input Voltage
(from UPS)
208V Switch Position
(L6-30R/L14-30R/5-15R)
Default 240V Switch Position
(L6-30R/L14-30R/5-15R)
208
208/240/120
208/208/104
220
220/252/126
220/220/110
230
230/262/131
230/230/115
240
240/272/136
240/240/120