INSTALLATION
EATON
Powerware
®
Energy Management System (EMS) Upgrade Kit User’s Guide
S
164201724 Rev 1
www.powerware.com
33
9.
The selected breaker is highlighted in
bold
in the schedule. The
breaker’s configuration details display in the right half of the page.
Click the breaker to configure. The breaker number highlights and
its details display at right.
10.
Configure the following settings for the selected breaker:
Breaker Setting
Description
Num Phases
Specify the number of phases (1–3).
Breaker Rating
Specify the branch breaker rating (in amps).
Warning Level
Specify the warning threshold level (in percent load).
Alarm Level
Specify the alarm threshold level (in percent load).
CT Ratio
Specify the current transformer ratio (75A).
NOTE
The selected ratio converts to the value 71.9.
NOTE
To revert any changes made on the current page back to default settings before
saving, click
Reload Breaker Config
.
11.
Repeat Steps 9 and 10 to configure the remaining breakers in the
panel.
12.
Click
Save Breaker Config
to save the settings to the EMS−UGK.
13.
Repeat Steps 8 through 12 to configure the breakers in the
remaining panels.
14.
Click
Disconnect
to disconnect from the EMS−UGK. Verify that Not
Connected" displays at the bottom of the page.
15.
Close the software configuration tool and remove the configuration
cable.
16.
Activate the reset switch on the bottom of the electronics module:
hold the switch for 10 seconds or until the display (if installed) turns
off, then release the switch.
17.
Continue to Advanced Metering Installation" on page 36.