42
A01-00134 Rev. A
ELECTRICAL
•
Output Voltage:
Select the
output rated voltage.
There are two options, 120V
and 127V. 120Vac is default
setting.
•
Output Rated FRE:
Select
output rated frequency
.
50Hz
: The output frequency is setting for 50Hz.
60Hz:
The output frequency is setting for 60Hz.
•
CVCF Mode (constant voltage and constant frequency function)
Enable:
CVCF function is enabled. The output frequency will be
fixed at 50Hz or 60Hz according to setting of “Output Freq.”. The
input frequency can range from 40Hz to 70Hz.
Disable:
CVCF function is disabled. The output frequency will
synchronize with the bypass frequency within 45~55 Hz for a 50Hz
system or within 55~65 Hz for a 60Hz system. Disable is the default
setting.
•
Bypass Forbid:
Enable:
Bypass Forbid is enabled. Running in Bypass mode is not
allowed under any situations.
Disable:
Bypass Forbid is disabled. UPS will run in Bypass mode. It
is the default setting.
•
Bypass at UPS off:
When
manually turning off the UPS,
select the bypass status.
This setting is only available
when “Bypass forbid” is set to
“Disable”.
Electrical Setting Page 1
Electrical Setting Page 2