ECO Voltage Range:
Set the ECO voltage range
.
•
•
L:
Low voltage point for ECO mode. The setting ranges from “rated
output voltage – 5V” to “Rated output voltage - 11V”. “Rated output
voltage – 5V” is default setting.
•
•
H:
High voltage point for ECO mode. The setting range is from “Rated
output v 5V” to “Rated output v 11V”. “Rated output
v 5V” is default setting.
•
ECO FRE Range:
Set the ECO frequency range. The setting ranges from
46Hz to 54Hz when the UPS is a 50Hz system and from 56Hz to 64Hz
when the UPS is a 60Hz system.
BATTERY
•
Battery Warning Voltage:
•
•
HIGH:
High battery warning
voltage. The setting range
is 14.0V ~ 15.0V. 14.4V is
default setting.
•
•
LOW:
Low battery warning
voltage. The setting range
is 10.1V ~ 14.0V. 11.4V
is default setting.
This
parameter setting is
related to the “Shutdown Voltage” setting. This setting value should be
higher than “Shutdown Voltage” setting.
•
Shutdown Voltage:
If battery voltage is lower than this point while in battery
mode, the UPS will automatically shut down. The setting range is 10.0V ~
12.0V. 10.7V is default setting. (The setting is only available for long-run
model)
•
Battery Parameter:
•
•
Battery AH:
setting battery capacity
. 9Ah is default setting.
Battery Setting Page