9. APPENDIX B : SPECIFICATIONS
UPS Model
ACDEF6000-22-1
ACDEF6000-22-4
UPS Part number
17602-02R
17602-03R
17602-04R
17602-05R
Topology
True On line, Double-Conversion
I
N
P
U
T
Voltage (VAC)
200, 208, 220, 230, 240
Voltage Range (VAC)
176 to 300 V + 3% @ Full load
110 to 300 V + 3% @ 1/2 load
Low Line Transfer - Batt
176 VAC + 3% @ Full load
110 VAC + 3% @ 1/2 load
Low Line Comeback
186 VAC + 3% @ Full load
120 VAC + 3% @ 1/2 load
High Line Transfer - Batt
300 VAC + 3%
High Line Comeback
290 VAC + 3%
Frequency (Hz)
50/60 (Auto-select on startup) + 4 Hz
Input PF
> 0.95 @ 100% load
Input Current THD
< 9 % Full Linear Load
Input Connection
Hardwire (screw terminal)
O
U
T
P
U
T
Capacity (208-240 Vout)
6000VA / 5400W
Capacity (200 Vout)
5400VA / 4800W
Rated Power Factor
0.9
Voltage (VAC)
208 V (Factory Default) 200 V, 220 V, 230 V, 240 V, Selectable
Waveform
Sinewave
Voltage Regulation
+/-1%
Output Voltage THD
< 3.0% (Linear Load), < 8.0% (Non-Linear Load)
Crest Factor
3:1 (max)
Frequency (Hz)
50/60
Frequency Regulation
± 0.1 Hz
Overload
(Transfer
to Bypass)
Line
Mode
100% - 110%: 10 min. typical
110% - 130%: 1 min. typical
>130%: 1 sec. typical
Battery
Mode
100% - 110%: 30 sec. typical
110% - 130%: 10 sec. typical
>130%: 1 sec. typical
Efficiency
AC-AC >84.0%
Output Connection (Full)
Hardwire (screw Terminals)
Output Receptacles
2 x IEC320-C19 (16Amp each)
Charger
Float Voltage
273 VDC
Current
1A +10% max.
1A +10% max.
4A +10% max.
4A +10% max.
B
Y
P
A
S
S
Bypass Activation
Automatic (Overload)
Manual (Front Panel Control)
Overload
100% - 130% (+ 5%) Continue carry load
>130% (+ 5%) Load Shutdown after 1 min.
Transfer time
0 ms