Smart-UPS X-Series 2000/2200/3000 VA Operation
General Settings
Configure these settings at any time, using the display interface, APC PowerChute
®
software, or a
network management card.
Function
Factory Default
Options
Description
High Transfer
Point
Low Voltage
To avoid unnecessary battery usage, set the
transfer point higher if the utility voltage is
chronically high and the connected
equipment is known to work under this
condition. The
P
OWER
Q
UALITY
setting will
automatically change this setting.
Note:
Use the Advanced Menus to configure
this setting.
100 V: 110 Vac
110-114 Vac
110 V: 116 Vac
116-125 Vac
120 V: 127 Vac
127-136 Vac
127 V: 134 Vac
134-143 Vac
High Voltage
200 V: 216 Vac
216-228 Vac
208 V: 225 Vac
225-237 Vac
220 V: 241 Vac
241-253 Vac
230 V: 253 Vac
253-265 Vac
240 V: 264 Vac
264-276 Vac
Low Transfer
Point
Low Voltage
Set the transfer point lower if the utility
voltage is chronically low and the connected
equipment can tolerate this condition.The
P
OWER
Q
UALITY
setting will automatically
change this setting.
Note:
Use the Advanced Menus to configure
this setting.
100 V: 92 Vac
86-92 Vac
110 V: 98 Vac
89-98 Vac
120 V: 106 Vac
97-106 Vac
127 V: 112 Vac
103-112 Vac
High Voltage
200 V: 184 Vac
172-184 Vac
208 V: 182 Vac
170-182 Vac
220 V: 199 Vac
187-199 Vac
230 V: 208 Vac
196-208 Vac
240 V: 216 Vac
204-216 Vac
Green Mode
If the UPS input voltage is between the high transfer point and the lower transfer point, the
unit will operate in green mode. Configure this setting using the Advanced menus.
Transfer
Sensitivity
Normal
• Normal
• Reduced
• Low
Select the level of sensitivity to power
events that the UPS will tolerate.
• Normal: The UPS will go on battery power
more often to provide the cleanest power
supply to the connected equipment.
• Reduced: The UPS will tolerate some
fluctuations in power.
• Low: The UPS will tolerate more
fluctuations in power and will go on
battery power less often.
If the connected load is sensitive to power
disturbances, set the sensitivity to High
using the advanced Configuration menu.
Low Runtime
Warning
150 sec
Set the value in
seconds
The UPS will emit an audible alarm when
the remaining runtime has reached this level.