PowerStar SMX2000RMLV2U Operation Manual Download Page 11

9

Smart-UPS X-Series 2000/2200/3000 VA  Operation

General Settings

Configure these settings at any time, using the display interface, APC PowerChute

®

 software, or a 

network management card.

Function

Factory Default

Options

Description

High Transfer 
Point 

Low Voltage

To avoid unnecessary battery usage, set the 
transfer point higher if the utility voltage is 
chronically high and the connected 
equipment is known to work under this 
condition. The 

P

OWER

 Q

UALITY

 setting will 

automatically change this setting. 

Note: 

Use the Advanced Menus to configure 

this setting.

100 V: 110 Vac

110-114 Vac

110 V: 116 Vac

116-125 Vac

120 V: 127 Vac

127-136 Vac

127 V: 134 Vac

134-143 Vac

High Voltage

200 V: 216 Vac

216-228 Vac

208 V: 225 Vac

225-237 Vac

220 V: 241 Vac

241-253 Vac

230 V: 253 Vac

253-265 Vac

240 V: 264 Vac

264-276 Vac

Low Transfer 
Point

Low Voltage

Set the transfer point lower if the utility 
voltage is chronically low and the connected 
equipment can tolerate this condition.The 

P

OWER

 Q

UALITY

 setting will automatically 

change this setting.

Note: 

Use the Advanced Menus to configure 

this setting.

100 V: 92 Vac

86-92 Vac

110 V: 98 Vac

89-98 Vac

120 V: 106 Vac

97-106 Vac

127 V: 112 Vac

103-112 Vac

High Voltage

200 V: 184 Vac

172-184 Vac

208 V: 182 Vac

170-182 Vac

220 V: 199 Vac

187-199 Vac

230 V: 208 Vac

196-208 Vac

240 V: 216 Vac

204-216 Vac

Green Mode 

If the UPS input voltage is between the high transfer point and the lower transfer point, the 
unit will operate in green mode. Configure this setting using the Advanced menus.

Transfer 
Sensitivity

Normal

• Normal
• Reduced
• Low

Select the level of sensitivity to power 
events that the UPS will tolerate.
• Normal: The UPS will go on battery power

more often to provide the cleanest power 
supply to the connected equipment.

• Reduced: The UPS will tolerate some

fluctuations in power.

• Low: The UPS will tolerate more

fluctuations in power and will go on 
battery power less often. 

If the connected load is sensitive to power 
disturbances, set the sensitivity to High 
using the advanced Configuration menu.

Low Runtime 
Warning

150 sec

Set the value in 
seconds

The UPS will emit an audible alarm when 
the remaining runtime has reached this level.

Summary of Contents for SMX2000RMLV2U

Page 1: ...Operation Smart UPS X UPS Low Voltage 100 127 V SMX2000RMLV2U SMX2200RMLV2U SMX3000RMLV2U SMX3000RMLV2UNC High Voltage 200 240 V SMX2200RMHV2U SMX3000RMHV2U SMX3000RMHV2UNC shipboard PS6003rm2u...

Page 2: ...Safety 1 Product Overview 1 Specifications 2 Installation 3 Operation 4 Connect Equipment to the UPS 4 Display Interface 5 Configuration 8 UPS Settings 8 Switched Outlet Groups 11 Emergency Power Off...

Page 3: ...PS has both high voltage 200 240 V and low voltage 100 127 V models Safety Read the Safety Guide included in the package before installing the UPS Inspect the UPS upon receipt Notify the carrier and d...

Page 4: ...e High temperatures poor utility power and frequent short duration discharges will shorten battery life For additional specifications see the APC Web site at www apc com Smart slot Controllable Outlet...

Page 5: ...agement Card For installation information see the user manual provided with the Network Management Card NMC The user manual is also available on the APC Web site at www apc com External Battery Pack F...

Page 6: ...a master on off switch turn on all the equipment that is connected to the UPS See Switched Outlet Groups on page 11 for information on how to use the Switched Outlet Groups Basic Connections Serial p...

Page 7: ...e advanced users to configure additional features of the unit Note Actual menu screens may differ by model Online indicator UPS Output On Off button On Battery indicator Fault indicator Replace Batter...

Page 8: ...x Audible alarms x x High and low transfer points x Low run time warning x Green mode x Output voltage x x Battery self test interval x x Battery installation date x x UPS firmware only available when...

Page 9: ...utput voltage setting serial number manufacture date replacement battery cartridge information firmware versions and suggested battery replacement date x x Smart Slot card information if applicable in...

Page 10: ...20 V 100 110 120 127 Set the nominal output voltage of the UPS is off High Voltage 230 V 200 208 220 230 240 Input Power Quality Good Good Fair Poor Select the quality of input utility power If Good i...

Page 11: ...Y setting will automatically change this setting Note Use the Advanced Menus to configure this setting 100 V 92 Vac 86 92 Vac 110 V 98 Vac 89 98 Vac 120 V 106 Vac 97 106 Vac 127 V 112 Vac 103 112 Vac...

Page 12: ...e display buttons are pressed Auto Self Test Interval Setting On start up and every 14 days since the last test Last test 14 days Last test 7 days Turn on 14 days Turn on 7 days On startup only Never...

Page 13: ...critical equipment to a Switched Outlet Group 2 Connect peripheral equipment to the other Switched Outlet Groups During a power outage to conserve battery runtime non essential equipment can be confi...

Page 14: ...lay Disabled When the unit switches to battery power the UPS can disconnect power to the Switched Outlet Groups to save runtime Configure this delay time use the LOAD SHED TIME WHEN ON BATTERY setting...

Page 15: ...1 is the power source for the EPO circuit it provides a few milliampere of 24 V power If the normally closed NC EPO configuration is used the EPO switch or relay should be rated for dry circuit appli...

Page 16: ...battery is weak due to a recent outage or is near the end of its service life Charge the battery Batteries require recharging after extended outages and wear out faster when put into service often or...

Page 17: ...nce with U S Department of Transportation DOT and IATA regulations The battery may remain in the unit c Internal batteries may remain connected in the XLBP during shipment if applicable not all units...

Page 18: ...D NO OBLIGATION OR LIABILITY WILL ARISE OUT OF APC s RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU O...

Page 19: ...APC by Schneider Electric APC the APC logo are owned by Schneider Electric Industries S A S American Power Conversion Corporation or their affiliated companies All other trademarks are property of th...

Reviews: