HYDROGUARD

® 

Thermostatic Tempering Valves 

ASSE 1017 Series LM490, LFLM490, LM490-10 and LFLM490-10

Installation Instructions

IS-P-LM490-LM490-10

NOTE:

 Installation should be in accordance with accept-

ed plumbing practices. Flush all pipes thoroughly before 

installation. Installation and field adjustment are the 

responsibility of the installer.

1.  Mark pipe as shown.  

This is pipe insertion depth.

2. Clean pipe end.

1. Remove collet clip.

2. Depress collet.
3. Pull tubing from tailpiece .

3.  If using PEX tubing, insert pipe stiff-

ener (provided) into end of pipe.

4.  Push tubing into tailpiece up to mark.
5. Insert collet clip.

PEX tubing only

Pipe Stiffener

Tail Piece

Mark

Collet clip

Collet depressed

1

1

/

2

 in. (38.1mm)

1

3

/

4

 in. (44.45mm)

1

7

/

8

 in. (47.63mm)

1

/

2

 in.Pipe (12.7mm)

3

/

4

 in.Pipe (19.05mm)

1 in.Pipe (25.4mm)

Vacuum Relief Valve

Temperatur

e Gauge

Cold

Cold

LM490, LFLM490,
LM490-10, LFLM490-10

8" - 10"

Temper

ed

Hot

Hot to Appliances 

T&P 

Relief Valve 

H

C

M

Cold

Figure 1.   

Domestic Hot Water Application

IMPORTANT:

To prolong the life of the series LM490, LFLM490, LM490-10 

or LFLM490-10 valves, it is recommended that the hot water 

inlet to the valve should be 8-10”(200-305 mm) below the hot 

water inlets.

1.   Close both hot and cold water shutoff valves upstream of 

the tempering valve.

2.   Bleed pressure from the system.
3.   Route copper tubing or piping to fit valve dimensions.
4.   For valves with Quick-Connect tailpieces refer to "Quick-

Connect Installation" instructions.

5.   Remove tailpieces from the valve and make sure union 

nuts are over the tubing/piping before connecting to the 

tailpiece.

NOTE:

  If soldering, remove unions and gaskets from valve 

body prior to soldering to prevent damage to valve from 

excessive heat.
6.   Flush piping again, install valve using filter gasket on hot 

and cold water inlets and fiber gasket on mixed water 

outlet.

7.   Turn on the cold and hot water. If any leak are observed, 

tighten connections as necessary to stop leak before pro-

ceeding.

LM490-5

LFLM490-1

Installation Instructions 

n

Quick-Connect Installation 

n

 

 TO CONNECT

  TO DISCONNECT

Advanced Thermal  

Activation