background image

PM

4025

Gaseous Fueled Stationary Standby

25

kW

60

Hz

General

Manufacturer

Ford

Model

LRG-425

Type

4-Cycle, In-line Configuration

Horsepower

45 Maximum (LP)@ 1800rpm

Cylinder Block Material

Cast Iron

Cylinders

4

Aspiration

Natural

Air Cleaner

Heavy Duty Replaceable Dry Element

Displacement

2.5 Liters

Compression Ratio

9.37:1

Bore

96mm

Stroke

86.3mm

RPM

1800

Engine Governing

± 0.5% - Electronic

Fuel System

     Fuel System

Woodward Fuel Mixer, Secondary Regulator, 12vdc Positive Locking Shut-off Solenoid

     Fuel Type

Liquefied Petroleum Gas(Vapor) Or Natural Gas

     Injection Method

Carburetor Induction

Lubrication  System

     Lube Oil System

Centrifugal Pump, Spin-on-Full Flow Filter

     Lube Oil Capacity

4.5 Quarts W/Filter

Cooling System

     Cooling System

105°F Ambient Radiator Equipped

     Ambient Operating Temperature Range

-20°F To 105°F

     Cooling System Capacity

2.8 Gallons

     Coolant Flow Rate

17.4 GPM

     Coolant Heater

120v, 500 Watt Thermostatically Controlled Circulation Type

Electrical

     Starting Voltage

12v negative ground

     Battery Size Required

BCI Group 26, Battery Rack & 2/0 Cables Included

     Cranking Current

550cca @ 0°F

     Battery Charging Alternator

90 amps

     Battery Charger (120v AC)

Bulk - 6A, 12vdc
Absorption - 5.5A, Taper To 1.5A Between 13-14.4vdc
Float – 0.1 To 0.3A, 13.3vdc 

Κ

 0.3vdc

Permits:

           California Air Resource Board

Consult Factory

           South Coast Air Quality Management

District

Consult Factory

Emissions Data* Tested To  ISO 8178 D2 Cycle:

            Hydrocarbons

Consult Factory

            Nitric Oxide

Consult Factory

            Carbon Monoxide

Consult Factory

            Particulate Matter

Consult Factory

Page 2 of 4

All Specifications Subject to Change Without Notice

©2002 Coleman Powermate, Inc.

Coleman® is a registered trademark of the Coleman Company, Inc. used under license.

Engine Data

Engine Emission Data

*Emission levels may rise above published limits due to improper maintenance or altered air intake/airflow.

Summary of Contents for PM4025

Page 1: ...t Motor Starting Tropicallized Windings Weather Enclosure 16 Gauge Steel Enclosure With Sound Material Installed Powder Painted Almond Color Finish Lockable keyed alike Doors With Sound Baffles Vertical Air Discharge For Optimal Sound Control Critical Grade Muffler Integral To Enclosure No Exterior Fasteners Fuel System Operates On Liquefied Petroleum Gas Or Natural Gas Simple Field Conversion Bet...

Page 2: ...ystem Capacity 2 8 Gallons Coolant Flow Rate 17 4 GPM Coolant Heater 120v 500 Watt Thermostatically Controlled Circulation Type Electrical Starting Voltage 12v negative ground Battery Size Required BCI Group 26 Battery Rack 2 0 Cables Included Cranking Current 550cca 0 F Battery Charging Alternator 90 amps Battery Charger 120v AC Bulk 6A 12vdc Absorption 5 5A Taper To 1 5A Between 13 14 4vdc Float...

Page 3: ...0 CFM Total Airflow 4550 CFM Heat Rejected To Coolant 70000 BTU HR Heat Rejected To Exhaust 195000 BTU HR Maximum Exhaust Flow 206 CFM Maximum Exhaust Backpressure 1 1 PSI Exhaust Temperature 1200 F Sound Data 66 66 66 66 dB A Average 23 7m Full Load dB A Average 23 7m Full Load dB A Average 23 7m Full Load dB A Average 23 7m Full Load 2002 Coleman Powermate Inc Coleman is a registered trademark o...

Page 4: ...erature Protection Engine Oil Pressure Monitoring Engine Oil Pressure Protection Overspeed Protection Overcrank Protection Emergency Stop Input Engine Cooldown Watt Metering VA Metering Engine RPM Metering Power Factor Metering Watt hour Metering Engine Run Time Metering Battery Voltage Metering Battery Condition Monitoring Maintenance Interval Timer On Off Auto Selector Switch Low Coolant Level D...