PROGRAMMING MANUAL • PH3 Mk II AIR INTAKE EMERGENCY SHUT-OFF VALVE 

L6493 

 

 

ECN 1-2212

 

L6493_Rev1

 

3

 

 

3

 

System Basics 

Controller settings are accessed and configured using 
toggle switch and Mode Selection Box. 

 

Mode Selection Box is located within harness. See 
Figure 3-A for summary of fuse positions. 

 

Fuses     F1     &     F2     are inserted or removed to 
access different modes. 

 

Mode Selection Box cap must be re-installed after 
use. 

 

Fuses     F1     &     F2     are used only for configuring 
modes and are not connected to main system power. 

 

3-A 

4

 

Quick Functions 

4.1

 

Manual Trip 

Manual Trip closes valve and causes engine (if running) to shut down. To perform Manual Trip: 

 

Push and release toggle switch 

4.2

 

Automatic / Manual Reset Mode 

To change valve behaviour between Auto/Manual Reset Mode access Mode Selection Box and: 

 

Remove fuse from     F2     on Mode Selection Box to select Auto Reset Mode 

OR

 

 

Insert fuse into     F2     on Mode Selection Box to select Manual Reset Mode 

4.3

 

Secondary Trip Speed 

System can force engine shutdown at 2 different engine speeds. Secondary Trip Speed can be used for protection of 
auxiliary equipment powered by Power Take-Off (PTO) system or as anti-theft mechanism when set near idle speed. 
To Activate, Program, or Test Secondary Trip Speed,  

 

Provide 6 to 36 VDC to Pink Wire (Pin 7 on Connector B). This can be done via existing PTO activation device 
or via latching switch (not provided). 

NOTE: To prevent accidental shut down while enabling/disabling Secondary Trip Speed, a 5 second grace period is 
applied when switching to a lower trip speed, to allow for engine speed to reduce. Change is applied immediately 
when switching to a higher trip speed.  