 PROGRAMMING MANUAL • PH5 AIR INTAKE EMERGENCY SHUT-OFF VALVE 

L6448 

 

 

ECN 1-1941

 

L6448_Rev3

 

2

 

 

1

 

Operation 

 

When the controller is unprogrammed, both lights will flash alternatingly 

 

When the engine is not running, neither light will flash on the controller 

 

When the engine is running, the green light should flash every 5 seconds to indicate the system is active and 
the engine speed is being monitored 

 

When the valve is closed, the red light will become lit and remain lit for 30 seconds 

 

When an emergency condition arises and an engine shutdown is needed, activate the toggle switch and the 
valve will close 

 

In an overspeed runaway condition, the PowerGuard controller will automatically close the valve and shut 
down the engine 

 

Once 30 seconds elapses, the red light will extinguish and the valve will be safe to reset 

 

Do NOT activate the toggle switch for more than 5 seconds 

2

 

Maintenance 

To ensure a trouble-free long life of your PowerHalt Shut-Off Valve, a scheduled monthly maintenance procedure is 
mandatory: 

 

Inspect all fasteners, clamps, and support brackets for tightness and the required torque 

 

Inspect all wiring / cable runs for corrosion, vibration wear, and loose connections 

 

Inspect all hoses for cracks, damage, and leaks 

 

Inspect the PowerGuard controller for damage, dirt, and poor connections 

 

Confirm the green light flashes every 5 seconds when the engine is running 

 

Activate the valve to ensure it remains functional and free moving 

 

Seizing due to lack of use is the #1 failure mode of any shut-off valve in the market. As this is a safety device, 
activation testing must be employed at a minimum of once per month. 

 

 

 