IMPORTANT SAFETY INSTRUCTION
S
1.
WARNING: SAVE THESE INSTRUCTIONS!!
This Manual Contains Important Instructions that should be followed during Installation and
Maintenance of the UPS
WARNING: Manual contains important instructions of UPS and batteries during installation and
maintenance. Follow this instruction at all time
WARNING:
It is recommended to install UPS in an ANSI/NFPA75 room in which temperature and humidity
are controlled and free from electrically conductive particles.
DO NOT
expose UPS to direct sunlight or
high heat source;
DO NOT
block off ventilation opening around the housing.
CAUTION:
Before conducting maintenance, repair, or shipment, please turn off everything completely
and disconnect them.
CAUTION:
The UPS is
NOT
applicable for any inductive loads such as motors or domestic appliances like
hairdryers, speakers, and fluorescent lamps.
CAUTION:
All interconnection and power cable should be connected
ONLY AFTER
the UPS shut down and
disconnected from main.
CAUTION:
Only use No.26 AWG or larger certified cables to connect UPS and device.
CAUTION:
DO NOT
unplug UPS from main power during operation or protective ground will fail.
DO NOT
disconnect battery under load or shut down may occur.
CAUTION:
Ensure the total leakage current of UPS and the connected equipment under 3.5mA.
CAUTION:
Ensure UPS connects to grounded main power with a fuse or circuit breaker protection.
CAUTION:
Dangerous amount of voltage might still exist even the UPS disconnects from the main power
since residual voltage exists due to battery supply.
CAUTION:
Beware of all the details on the cautionary sticker located on UPS.
CAUTION (No user-serviceable parts):
Do not attempt to remove the unit’s cover, no user-serviceable
parts inside. Please refer all service to qualified service technicians.
CAUTION:
DO NOT
dispose UPS and its batteries to fire, the battery may explode.
CAUTION:
DO NOT
attempt to open or mutilate the battery.
User’s operations
: Users only permits to:
• Turning the UPS unit on and off.
• Operating the user interface.
• Connecting data interface cables.
• Changing the batteries.
CAUTION:
Servicing of batteries should be performed or supervised by personnel knowledgeable of
batteries and the required precautions. Keep unauthorized personnel away from battery
CAUTION:
To reduce the risk of fire, connect only to a circuit provided with 20 amperes maximum branch
circuit overcurrent protection in accordance with the National Electrical Code, ANSI/NFPA 70.
CAUTION:
Maximum ambient temperature 30°C
CAUTION:
Intended for Installation in a Controlled Environment.
DANGER:
Hazardous electric component inside this unit (example: Heat-sinks) remain energized from the
battery supply even when the main power is disconnected.
DANGER:
Battery circuit is not isolated from the AC input. Hazardous voltage may exist at battery
terminals and ground—test for safety before any direct contact.
CAUTION:
Remove the battery’s pole during service inside the battery cabinet or UPS.
CAUTION:
ONLY
replace batteries with the same type and quantity.
WARNING (Fuses)
: Ensure fuse replacement with the same type and rating
ONLY
.
2.
Introduction
The information provided in this manual covers Line-Interactive 1025-3000VA
uninterruptible power
system (UPS). This manual contains basic functions, operating procedures, and emergencies, also including
information on how to ship, store, handle, and install the equipment. Only detailed requirements of the UPS
units described herein. The installation must carry out according to this manual. The electrical installation
must further comply with local legislation and regulations.
3.
Installation
3.1 Rear panel view
*Figures only display available function; functions are not on unit if not marked.