19
10: Reserved
I nterface
Setting
Reserved
11: Reserved
I nterface
Setting
Reserved
12: Hot standby function enable/ disable
I nterface
Setting
Parameter 2: HS.H
Enable or disable Hot standby function. You may choose following
two options in
Parameter 3
:
YES:
Hot standby function is enabled. I t means that the current
UPS is set to host of the hot standby function, and it will restart
after AC recovery even without battery connected.
NO:
Hot standby function is disabled. The UPS is running at
normal mode and can’t restart without battery
13: Battery voltage adjustment
I nterface
Setting
Parameter 2:
Select “
Add
” or “
Sub
” function to adjust battery
voltage to real figure.
Parameter 3:
the voltage range is from 0V to 5.7V, the default
value is 0V.
14: Charger voltage adjustment
I nterface
Setting
Parameter 2:
you may choose
Add
or
Sub
to adjust charger
voltage
Parameter 3:
the voltage range is from 0V to 9.9V, the default
value is 0V.
NOTE:
* Before making voltage adjustment, be sure to disconnect all
batteries first to get the accurate charger voltage.
* We strongly suggest to use the default value (0). Any
modification should be suitable to battery specifications.