16
3- 7. LCD Setting
There are three parameters to set up the UPS. Refer to following diagram.
Programs available list for parameter 1:
Code
Description
Bypass/
No output
AC
ECO
CVCF
Battery
Battery
Test
01
Output voltage
Y
02
Output frequency
Y
03
Voltage range for bypass
Y
04
Frequency range for bypass
Y
05
ECO mode enable/ disable
Y
06
Voltage range for ECO mode
Y
07
ECO mode frequency range setting
Y
08
Bypass mode setting
Y
Y
09
Battery backup time setting
Y
Y
Y
Y
Y
Y
10
Reserved
Reserved for future
11
Reserved
Reserved for future
12
Hot standby function enable/ disable
Y
Y
Y
Y
Y
Y
13
Battery voltage adjustment
Y
Y
Y
Y
Y
Y
14
Charger voltage adjustment
Y
Y
Y
Y
Y
Y
15
I nverter voltage adjustment
Y
Y
Y
16
Output voltage calibration
Y
Y
Y
* Y means that this program can be set in this mode.
Note: All parameter settings will be saved only when UPS shuts down normally with internal or external battery
connection. (Normal UPS shutdown means turning off input breaker in bypass mode).
01: Output voltage
I nterface
Setting
Parameter 3: Output voltage
You may choose the following output voltage in parameter 3:
208:
Presents output voltage is 208Vac
220:
Presents output voltage is 220Vac
230:
Presents output voltage is 230Vac
240:
Presents output voltage is 240Vac
Parameter 1
Parameter 2
Parameter 3
Parameter 1: I t ’s for program alternatives. There
are 16 programs to set up. Refer to below table.
Parameter 2 and parameter 3 are the setting
options or values for each program.