277V Input Power & Field Connection Diagram
(
See pages 11-13
for control wiring information)
Note that regulation at 277V is inferior to using 240V
. 277V operation is provided
for convenience and ease of installation. When using the integrated battery flash,
flashing performance may improve when using 277V instead of 240V connection.
This connection is typically used on generators with full load field voltages of 63VDC or
less and full load exciter field amperage less than 12ADC.
Note that the maximum input voltage to the XC15
Voltage regulator in this
connection is 277VAC!
DO NOT input 480VAC into the XC15
in this connection!
Regulation problems or damage to the unit may result! For use on 480V systems,
connect the regulator from Line to Neutral T7 and T0 (
See Pages 6 and 7
), or use a
480-240V step-down transformer rated at 1KVA
.
Diagram Assumes a 480V Generator
For other voltages, use a 1KVA
(or larger)
Transformer
with a
240V Secondary
.
NEVER install a switch or
breaker on the DC or Exciter
side of the voltage regulator!
Only install a switch or
disconnect on the AC Side of
the regulator!
See Page 11 for
Paralleling Wire
Diagram
100KΩ @ 2w
NOTE:
It is not necessary
to jumper terminals
R1 and R2 if not
using the Remote
Voltage Adjustment!
NOTE:
Jumper
X & Y if
generator
is not
paralleled!
See Pages 12-13
for External
Control Wiring
Diagrams
See Page 14 for
Battery Flash
Wiring Diagram
NOTE:
Use Double-Throw
switch rated:
20A @ 250VAC
2
nd
Circuit Used
for Battery