11
Current Transformer Wiring Diagram
For Paralleled Generators
To use the XC14
Voltage regulator in a parallel configuration either with another
generator or with a buss such as a utility, use the diagram below for proper hookup with
the XC14.
Power and field wiring is shown on Pages 8-10.
This diagram assumes a paralleled operating environment
with manual remote adjustment.
NOTE:
Power-Tronics products parallel using the Reactive Droop compensation method. This allows
our products to parallel with existing systems easily while also allowing islanded operation with the flip of
a switch.
When initially installing the droop resistor, set it for approximately 7Ω before final
adjustment later.
If the droop is excessive when load testing, reduce the resistance a bit at a time until
satisfactory droop is achieved.
CT should be sized at 25-35VA capacity!
xxx/5a CT
25-35VA
Unit/Parallel
Switch
Reactive Droop
Adjustment
10Ω, 100W
If using the
internal 0-10VDC
Interface module,
See Pages 12-13
for Control Wiring
Diagrams
NOTE:
Don’t Omit Remote
Adjustment on a
Paralleled Generator!!!
100KΩ @ 2w