APPLIANCE LOADS
Generator sets in recreational vehicles are often used to supply AC voltage for appliances. With
the exception of a resistance-type load such as a water heater, requirements for appliances are usually
low. However, such loads must not be overlooked when calculating the total wattage requirements. To
avoid an overload situation, reserve capacity should also be calculated for unanticipated appliance loads.
The average power requirements for some common electrical appliances are listed below as a guide.
DETERMINING ALTERNATOR LOAD REQUIREMENTS
CHECK
√
APPLIANCE
WATTS
REQUIRED
VCR
70
LIGHT
BULB
100
RADIO
100
TELEVISION
100
STEREO
100
FRY
PAN
150
HOME
COMPUTER
150
VACUUM
CLEANER
250
ATTIC FAN 1/4 HP
400
SUMP PUMP 1/3 HP
500
REFRIGERATOR
500
FURNACE FAN 1/3 HP
600
FREEZER
800
JET WATER PUMP ¾ HP
900
ELECTRIC STOVE ELEMENT
1000
SUBMERSIBLE WATER PUMP 1 HP
1000
TOASTER
1000
COFFEE
MAKER
1200
DISHWASHER
1200
HAIR
DRYER
1200
MICROWAVE
OVEN
1500
SUBMERSIBLE WATER PUMP 2 HP
1600
WATER
HEATER
3000
OVEN
4500
TOTAL WATTS CHECKED
EXTENSION CORDS
An extension cord is normally used to provide electrical power from the generator set to a remote
location. The extension cord size (AWG#) and length must be adequate to safely maintain the amperage
requirements. A proper size extension cord will help minimize the voltage drop between the generator
set and remote location.
AMPS
LOAD IN WATTS
CORD LENGTH
120 VOLTS
240 VOLTS
AWG#10
AWG#12
AWG#14
5
600
1200
500 FT
300 FT
200 FT
10
1200
2400
250 FT
150 FT
100 FT
20
2400
4800
125 FT
75 FT
50 FT
30
3600
7200
60 FT
35 FT
25 FT
40
4800
9600
30 FT
15 FT
10 FT
50 6000 12000
15
FT
-----
-----
15