Engine Runs OK
Has
Power
NO
Power
Has Power
NO Power
Engine runs OK NO Power
8
ENGINE STARTS
BUT WON’T RUN
Unplug Remote
Start-Stop from
Control Box
Problem with
Remote Connection.
Contact
Equipment Manufacturer
Jump across
Oil Pressure Switch
with Jumper Wire
(2 pole)
Check Power
to Hold Circuit
of Run Solenoid
Check
Oil Pressure
With Gauge
Replace
Oil Pressure Switch
Defective Solenoid
REPLACE
Plug Remote
Back IN
Remote OK
Problem with Remote
Check
Safety Shutdown
System
Remove Wire From
Water Temperature Switch
Replace Water
Temperature
Switch
Check Shutdown
Relay
Check Wiring
Oil Pressure Switch
Single Pole
Disconnect Wire to Test
If “OK”
Replace
Switch