SAFETY CAUTION 

SAVE THESE INSTRUCTION-This manual contains important instructions that should be 
followed during installation and maintenance of the UPS and batteries. 

1) This UPS utilizes voltage that may be hazardous. Do not attempt to disassemble the unit. 
The unit contains no user replaceable parts. Only factory service personnel may perform 
repairs. 

2) This pluggable type a equipment with battery already installed by the supplier is operator 
installable and may be operated by laymen. 

3) The mains socket outlet that supplies the UPS shall be installed near the UPS and shall 
be easily accessible. 

4) During the installation of this equipment it should be assured that the sum of the leakage 
currents of the UPS and the connected loads does not exceed 3.5mA. 

5) Connection to any other type of receptacle other than a two-pole, three-wire grounded 
receptacle may result in shock hazard as well as violate local electrical codes. 

6) In the event of an emergency, press the "OFF" button and disconnect the power cord from 
the AC power supply to properly disable the UPS. 

7) Do not allow any liquids or any foreign object to enter the UPS. Do not place beverages or 
any other liquid-containing vessels on or near the unit. 

8) This unit intended for installation in a controlled environment (temperature controlled, 
indoor area free of conductive contaminants). Avoid installing the UPS in locations where 
there is standing or running water, or excessive humidity. 

9) Do not plug the UPS input into its own output. 

10) Do not attach a power strip or surge suppressor to the UPS. 

Do not attach non-computer-related items, such as medical equipment, life-support 
equipment, microwave ovens, or vacuum cleaners to UPS. 

11) Do not dispose of batteries in a fire as they may explode. 

12) A battery can present a risk of electrical shock and high short circuit current. The 
following precautions should be observed when working on batteries: 

Remove watches, rings, or other metal objects from the hands. 

Use tools with insulated handles. 

Wear rubber gloves and boots. 

Do not lay tools or metal parts on top of batteries. 

Disconnect charging source prior to connecting or disconnecting batteries terminal. 

 

 

Summary of Contents for PS-PGU1500VA#2B9A

Page 1: ......

Page 2: ... unit Connect Communication Cable To allow for unattended UPS shutdown start up and status monitoring connect the communication cable one end to the USB port and the other to the communication port of your PC With the monitoring software installed you can schedule UPS shutdown start up and monitor UPS status through PC Turn On Off the UPS Turn on the UPS unit by pressing the power switch Then the ...

Page 3: ...cted area that is free of excessive dust and has adequate air flow Place the UPS away from other units at least 20 cm to avoid interference For best performance keep the indoor temperature between 0 C and 40 C Storage All connected equipment should be turned off then disconnect from the UPS to avoid battery drain Unplug the UPS from the wall outlet Then turn off the UPS for storage Store the UPS u...

Page 4: ...PRODUCT OVERVIEW FRONT PANEL 1 LCD display 2 RGB lights 3 Power switch 4 5V USB port REAR PANEL ...

Page 5: ...1 Output socket 2 USB port 3 Circuit breaker 4 AC input ...

Page 6: ... Input voltage 3 Load level 4 Battery capacity Overload in AC mode When overload occurs alarm will beep every 0 5 second Battery Mode Alarm will beep every 10 seconds and LCD information will be displayed in the following order when LCD is touched 1 Output voltage 2 Input voltage 3 Load level 4 Battery capacity Overload in Battery mode When overload occurs alarm will beep every 0 5 second ...

Page 7: ...and disconnect the power cord from the AC power supply to properly disable the UPS 7 Do not allow any liquids or any foreign object to enter the UPS Do not place beverages or any other liquid containing vessels on or near the unit 8 This unit intended for installation in a controlled environment temperature controlled indoor area free of conductive contaminants Avoid installing the UPS in location...

Page 8: ...ous through electric shock Also with dis connection of this unit from the mains hazardous voltage still may be accessible through supply from battery The battery supply should be therefore disconnected in the plus and minus pole at the connectors of the battery when maintenance or service work inside the UPS is necessary 17 To reduce the risk of overheating the UPS do not cover the UPS cooling ven...

Page 9: ... 60Hz 1 Output Voltage range V 220V 10 Transfer time Typical 4 6ms Waveform Simulated Sine Wave Battery Type 12V9AH 2 Typical recharge time 8 hours recover to 90 capacity Dimension mm 330 115 265 Weight Kg 20kg Humidity 0 90 RH 0 40 non condensing Noise Level Less than 50dB USB Communication Port YES 5V USB 2pcs RGB light 2pcs ...

Page 10: ...battery The UPS always on battery mode Power cord loose Re plug the power cord Backup time too short Battery voltage is too low Charge the battery at least 6 hours Overload Remove some unnecessary loads Before reconnecting equipment please verify that the load matches the UPS capability specified in the specs Battery defect Replace the battery If any abnormal situations occur that are not listed a...