background image

16 

 

 

4. Troubleshooting 

If the UPS system does not operate correctly, please solve the problem by using the table below.   

Symptom 

Possible cause 

Remedy 

No indication and alarm even 
though the mains is normal.   

The AC input power is not 
connected well. 

Check  if  input  power  cord 
firmly  connected  to  the 

mains.   

The  AC  input  is  connected 
to the UPS output. 

Plug AC input power cord to 
AC input correctly.   

The icon 

and 

  flashing on 

LCD display and alarm is sounding 
every second. 

The external or internal 

battery is incorrectly 
connected. 

Check  if  all  batteries  are 

connected well. 

Fault code is shown as 27 and the 

icon 

 

is lighting on LCD 

display and alarm is continuously 
sounding. 

Battery voltage is too  high 
or the charger is fault. 

Contact your dealer. 

Fault code is shown as 28 and the 

icon 

 

is lighting on LCD 

display and alarm is continuously 

sounding. 

Battery  voltage  is  too  low 
or the charger is fault. 

Contact your dealer. 

The icon 

  and

is 

flashing on LCD display and alarm 

is sounding twice every second. 

UPS is overload   

Remove  excess  loads  from 
UPS output. 

UPS is overloaded. Devices 
connected to the UPS are 

fed directly by the electrical 
network via the Bypass. 

Remove  excess  loads  from 
UPS output. 

After repetitive overloads, 
the UPS is locked in the 

Bypass mode. Connected 
devices are fed directly by 
the mains. 

Remove  excess  loads  from 
UPS output first. Then shut 

down  the  UPS  and  restart 
it. 

Fault code is shown as 43 and The 

icon 

 

is lighting on LCD 

display and alarm is continuously 
sounding. 

The UPS shut down 

automatically because of 
overload at the UPS output. 

Remove  excess  loads  from 

UPS output and restart it. 

Fault code is shown as 14 and the 
icon 

 

is lighting on LCD 

display and alarm is continuously 
sounding. 

The UPS shut down 
automatically because 
short circuit occurs on the 
UPS output. 

Check  output  wiring  and  if 
connected  devices  are  in 
short circuit status. 

Fault code is shown as 01, 02, 03, 

04, 11, 12, 13, 41 and 45 on LCD 
display and alarm is continuously 
sounding. 

A  UPS  internal  fault  has 

occurred.  There  are  two 
possible results: 
1. The load is still supplied, 

but directly from AC power 
via bypass.   
2.  The  load  is  no  longer 

supplied by power.   

Contact your dealer 

Summary of Contents for VFI-C Series 1KR

Page 1: ...VFI C Series 1K 2K 3K Online UPS Uninterruptible Power Supply System Version 1 1...

Page 2: ...2 2 Installation and setup 3 2 1 Rear panel view 3 2 2 Setup the UPS 7 3 Operations 9 3 1 Button operation 9 3 2 LCD Panel 9 3 3 Audible Alarm 11 3 4 LCD display wordings index 11 3 5 UPS Setting 11...

Page 3: ...er them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed sh...

Page 4: ...must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the...

Page 5: ...thing inside the package is damaged Please keep the original package in a safe place for future use 2 1 Rear panel view 1K India Type IEC Type NEMA Type Schuko Type Universal Type 1KL India Type IEC T...

Page 6: ...4 2KL India Type IEC Type Schuko Type Universal Type 3K India Type IEC Type NEMA Type Schuko Type Universal Type 3KL India Type IEC Type Schuko Type Universal Type 1KR IEC Type Universal Type...

Page 7: ...5 China Type 2KR IEC Type Universal Type China Type 3KR IEC Type Universal Type China Type 1KRL IEC Type Universal Type...

Page 8: ...Universal Type China Type 1 AC input 2 Input circuit breaker 3 USB communication port 4 RS 232 communication port 5 SNMP intelligent slot option 6 External battery connection only available for L mod...

Page 9: ...status monitoring connect the communication cable one end to the USB RS 232 port and the other to the communication port of your PC With the monitoring software installed you can schedule UPS shutdown...

Page 10: ...8 Step 6 External battery connection This UPS is not including batteries Please connect external batteries as below chart...

Page 11: ...in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button Confirm selection key Press this button to confirm selection in UPS setting mode Sele...

Page 12: ...frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuit Mode operation information Indicates the UP...

Page 13: ...re CH Charger FU Bypass frequency unstable EE EEPROM error 3 5 UPS Setting There are three parameters to set up the UPS Parameter 1 It s for program alternatives Refer to below table Parameter 2 and p...

Page 14: ...t frequency is 60Hz If converter mode is enabled you may choose the following output frequency CF 50 presents output frequency is 50Hz CF 60 presents output frequency is 60Hz 04 ECO enable disable Int...

Page 15: ...in parameter 3 from 230Vac to 264Vac Default 264Vac For 100 110 115 120 127 VAC models 115 132 setting the high voltage point in parameter 3 from 115Vac to 132Vac Default 132Vac LLS Bypass low voltage...

Page 16: ...er mode When input frequency is within 40 Hz to 70 Hz the UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge battery under this mode Battery mode When the input vol...

Page 17: ...ltage high 12 x Charger failure 45 x Inverter voltage Low 13 x 3 8 Warning indicator Warning Icon flashing Alarm Low Battery Sounding every second Overload Sounding twice every second Battery is not c...

Page 18: ...e every second UPS is overload Remove excess loads from UPS output UPS is overloaded Devices connected to the UPS are fed directly by the electrical network via the Bypass Remove excess loads from UPS...

Page 19: ...up time is shorter than nominal value Batteries are not fully charged Charge the batteries for at least 5 hours and then check capacity If the problem still persists consult your dealer Batteries defe...

Page 20: ...ler Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperatur...

Page 21: ...1 Harmonic Distortion 3 THD linear load 6 THD non linear load Transfer Time AC Mode to Batt Mode Zero Inverter to Bypass 4 ms Typical Waveform Batt Mode Pure Sinewave EFFICIENCY AC Mode 88 89 90 Batt...

Page 22: ...Current Crest Ratio 3 1 Harmonic Distortion 3 THD linear load 6 THD non linear load Transfer Time AC Mode to Batt Mode Zero Inverter to Bypass 4 ms Typical Waveform Batt Mode Pure Sinewave EFFICIENCY...

Page 23: ...21 Note...

Page 24: ...22 Power Inspired Ltd Units 5 7 High Point Riding Road Buckingham Road Industrial Estate Brackley Northamptonshire NN13 7BH United Kingdom www powerinspired com...

Reviews: