background image

12 

 

230:

 presents output voltage is 230Vac (Default) 

240:

 presents output voltage is 240Vac 

For 100/110/150/120/127 VAC models, you may choose 
the following output voltage: 

100:

 presents output voltage is 100Vac 

110:

 presents output voltage is 110Vac 

115: 

presents output voltage is 115Vac 

120: 

presents output voltage is 120Vac (Default) 

127: 

presents output voltage is 127Vac 

 

02: Frequency Converter enable/disable 

Interface 

Setting 

 

Parameter 2 & 3: 

Enable or disable converter mode. You 

may choose the following two options:

 

CF ENA: 

converter mode enable 

CF DIS: 

converter mode disable(Default) 

 

03: Output frequency setting 

Interface 

Setting 

 

Parameter 2 & 3: Output frequency setting.   

You may set the initial frequency on battery mode: 

BAT 50:

 presents output frequency is 50Hz 

BAT 60:

 presents output frequency is 60Hz 

If converter mode is enabled, you may choose the 
following output frequency: 

CF 50: 

presents output frequency is 50Hz 

CF 60: 

presents output frequency is 60Hz 

 

04: ECO enable/disable 

Interface 

Setting 

 

Parameter 3: 

Enable or disable ECO function. You may 

choose the following two options:   

ENA:

 ECO mode enable 

DIS: 

ECO mode disable (Default) 

 

05: ECO voltage range setting 

Interface 

Setting 

 

Parameter 2 & 3: 

Set the acceptable high voltage point 

and low voltage point for ECO mode by pressing Down key 
or Up key.     

HLS: 

High loss voltage in ECO mode

 

in parameter 2. 

For 200/208/220/230/240 VAC models, the setting range 
in parameter 3 is from +7V to +24V of the nominal voltage. 
(Default: +12V) 
For 100/110/115/120/127 VAC models, the setting range 

in parameter 3 is from +3V to +12V of the nominal voltage. 
(Default: +6V) 

LLS: 

Low loss voltage in ECO mode in parameter 2. 

For 200/208/220/230/240 VAC models, the setting range 
in parameter 3 is from -7V to -24V of the nominal voltage.   
(Default: -12V)   

Summary of Contents for VFI-C Series 1KR

Page 1: ...VFI C Series 1K 2K 3K Online UPS Uninterruptible Power Supply System Version 1 1...

Page 2: ...2 2 Installation and setup 3 2 1 Rear panel view 3 2 2 Setup the UPS 7 3 Operations 9 3 1 Button operation 9 3 2 LCD Panel 9 3 3 Audible Alarm 11 3 4 LCD display wordings index 11 3 5 UPS Setting 11...

Page 3: ...er them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed sh...

Page 4: ...must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the...

Page 5: ...thing inside the package is damaged Please keep the original package in a safe place for future use 2 1 Rear panel view 1K India Type IEC Type NEMA Type Schuko Type Universal Type 1KL India Type IEC T...

Page 6: ...4 2KL India Type IEC Type Schuko Type Universal Type 3K India Type IEC Type NEMA Type Schuko Type Universal Type 3KL India Type IEC Type Schuko Type Universal Type 1KR IEC Type Universal Type...

Page 7: ...5 China Type 2KR IEC Type Universal Type China Type 3KR IEC Type Universal Type China Type 1KRL IEC Type Universal Type...

Page 8: ...Universal Type China Type 1 AC input 2 Input circuit breaker 3 USB communication port 4 RS 232 communication port 5 SNMP intelligent slot option 6 External battery connection only available for L mod...

Page 9: ...status monitoring connect the communication cable one end to the USB RS 232 port and the other to the communication port of your PC With the monitoring software installed you can schedule UPS shutdown...

Page 10: ...8 Step 6 External battery connection This UPS is not including batteries Please connect external batteries as below chart...

Page 11: ...in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button Confirm selection key Press this button to confirm selection in UPS setting mode Sele...

Page 12: ...frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuit Mode operation information Indicates the UP...

Page 13: ...re CH Charger FU Bypass frequency unstable EE EEPROM error 3 5 UPS Setting There are three parameters to set up the UPS Parameter 1 It s for program alternatives Refer to below table Parameter 2 and p...

Page 14: ...t frequency is 60Hz If converter mode is enabled you may choose the following output frequency CF 50 presents output frequency is 50Hz CF 60 presents output frequency is 60Hz 04 ECO enable disable Int...

Page 15: ...in parameter 3 from 230Vac to 264Vac Default 264Vac For 100 110 115 120 127 VAC models 115 132 setting the high voltage point in parameter 3 from 115Vac to 132Vac Default 132Vac LLS Bypass low voltage...

Page 16: ...er mode When input frequency is within 40 Hz to 70 Hz the UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge battery under this mode Battery mode When the input vol...

Page 17: ...ltage high 12 x Charger failure 45 x Inverter voltage Low 13 x 3 8 Warning indicator Warning Icon flashing Alarm Low Battery Sounding every second Overload Sounding twice every second Battery is not c...

Page 18: ...e every second UPS is overload Remove excess loads from UPS output UPS is overloaded Devices connected to the UPS are fed directly by the electrical network via the Bypass Remove excess loads from UPS...

Page 19: ...up time is shorter than nominal value Batteries are not fully charged Charge the batteries for at least 5 hours and then check capacity If the problem still persists consult your dealer Batteries defe...

Page 20: ...ler Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperatur...

Page 21: ...1 Harmonic Distortion 3 THD linear load 6 THD non linear load Transfer Time AC Mode to Batt Mode Zero Inverter to Bypass 4 ms Typical Waveform Batt Mode Pure Sinewave EFFICIENCY AC Mode 88 89 90 Batt...

Page 22: ...Current Crest Ratio 3 1 Harmonic Distortion 3 THD linear load 6 THD non linear load Transfer Time AC Mode to Batt Mode Zero Inverter to Bypass 4 ms Typical Waveform Batt Mode Pure Sinewave EFFICIENCY...

Page 23: ...21 Note...

Page 24: ...22 Power Inspired Ltd Units 5 7 High Point Riding Road Buckingham Road Industrial Estate Brackley Northamptonshire NN13 7BH United Kingdom www powerinspired com...

Reviews: