3. Operations 
3-1. Button operation 

Button 

Function   

ON/Mute Button   

 

Turn on the UPS: Press and hold ON/Mute button for at least 2 seconds 
to turn on the UPS. 

 

Mute the alarm: When the UPS is on battery mode, press and hold this 

button for at least 5 seconds to disable or enable the alarm system. But 
it

s not applied to the situations when warnings or errors occur.   

 

Up key: Press this button to display previous selection in UPS setting 
mode. 

 

Switch to UPS self-test mode: Press and hold ON/Mute button for 5 

seconds to enter UPS self-testing while in AC mode, ECO mode, or 
converter mode. 

OFF/Enter Button   

 

Turn off the UPS: Press and hold this button at least 2 seconds to turn 
off the UPS. UPS will be in standby mode under power normal or 
transfer to Bypass mode if the Bypass enable setting by pressing this 

button.   

 

Confirm selection key: Press this button to confirm selection in UPS 
setting mode.   

Select Button   

 

Switch LCD message: Press this button to change the LCD message for 

input voltage, input frequency, battery voltage, output voltage and 
output frequency. It will return back to default display when pausing 
for 10 seconds.   

 

Setting mode: Press and hold this button for 5 seconds to enter UPS 
setting mode when UPS is in standby mode or bypass mode.   

 

Down key: Press this button to display next selection in UPS setting 
mode. 

ON/Mute + Select 

Button 

 

Switch to bypass mode: When the main power is normal, press 
ON/Mute and Select buttons simultaneously for 5 seconds. Then UPS 
will enter to bypass mode. This action will be ineffective when the 
input voltage is out of acceptable range.   

 

3-2. LCD Panel 

 

 

Summary of Contents for VFI-C Series 1KR

Page 1: ...VFI C Series 1K 2K 3K Online UPS Uninterruptible Power Supply System Version 1 1...

Page 2: ...2 2 Installation and setup 3 2 1 Rear panel view 3 2 2 Setup the UPS 7 3 Operations 9 3 1 Button operation 9 3 2 LCD Panel 9 3 3 Audible Alarm 11 3 4 LCD display wordings index 11 3 5 UPS Setting 11...

Page 3: ...er them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed sh...

Page 4: ...must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the...

Page 5: ...thing inside the package is damaged Please keep the original package in a safe place for future use 2 1 Rear panel view 1K India Type IEC Type NEMA Type Schuko Type Universal Type 1KL India Type IEC T...

Page 6: ...4 2KL India Type IEC Type Schuko Type Universal Type 3K India Type IEC Type NEMA Type Schuko Type Universal Type 3KL India Type IEC Type Schuko Type Universal Type 1KR IEC Type Universal Type...

Page 7: ...5 China Type 2KR IEC Type Universal Type China Type 3KR IEC Type Universal Type China Type 1KRL IEC Type Universal Type...

Page 8: ...Universal Type China Type 1 AC input 2 Input circuit breaker 3 USB communication port 4 RS 232 communication port 5 SNMP intelligent slot option 6 External battery connection only available for L mod...

Page 9: ...status monitoring connect the communication cable one end to the USB RS 232 port and the other to the communication port of your PC With the monitoring software installed you can schedule UPS shutdown...

Page 10: ...8 Step 6 External battery connection This UPS is not including batteries Please connect external batteries as below chart...

Page 11: ...in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button Confirm selection key Press this button to confirm selection in UPS setting mode Sele...

Page 12: ...frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuit Mode operation information Indicates the UP...

Page 13: ...re CH Charger FU Bypass frequency unstable EE EEPROM error 3 5 UPS Setting There are three parameters to set up the UPS Parameter 1 It s for program alternatives Refer to below table Parameter 2 and p...

Page 14: ...t frequency is 60Hz If converter mode is enabled you may choose the following output frequency CF 50 presents output frequency is 50Hz CF 60 presents output frequency is 60Hz 04 ECO enable disable Int...

Page 15: ...in parameter 3 from 230Vac to 264Vac Default 264Vac For 100 110 115 120 127 VAC models 115 132 setting the high voltage point in parameter 3 from 115Vac to 132Vac Default 132Vac LLS Bypass low voltage...

Page 16: ...er mode When input frequency is within 40 Hz to 70 Hz the UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge battery under this mode Battery mode When the input vol...

Page 17: ...ltage high 12 x Charger failure 45 x Inverter voltage Low 13 x 3 8 Warning indicator Warning Icon flashing Alarm Low Battery Sounding every second Overload Sounding twice every second Battery is not c...

Page 18: ...e every second UPS is overload Remove excess loads from UPS output UPS is overloaded Devices connected to the UPS are fed directly by the electrical network via the Bypass Remove excess loads from UPS...

Page 19: ...up time is shorter than nominal value Batteries are not fully charged Charge the batteries for at least 5 hours and then check capacity If the problem still persists consult your dealer Batteries defe...

Page 20: ...ler Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperatur...

Page 21: ...1 Harmonic Distortion 3 THD linear load 6 THD non linear load Transfer Time AC Mode to Batt Mode Zero Inverter to Bypass 4 ms Typical Waveform Batt Mode Pure Sinewave EFFICIENCY AC Mode 88 89 90 Batt...

Page 22: ...Current Crest Ratio 3 1 Harmonic Distortion 3 THD linear load 6 THD non linear load Transfer Time AC Mode to Batt Mode Zero Inverter to Bypass 4 ms Typical Waveform Batt Mode Pure Sinewave EFFICIENCY...

Page 23: ...21 Note...

Page 24: ...22 Power Inspired Ltd Units 5 7 High Point Riding Road Buckingham Road Industrial Estate Brackley Northamptonshire NN13 7BH United Kingdom www powerinspired com...

Reviews: