background image

15

NOVA PLUS Installation & Operation Manual - 

POWER FLAME INCORPORATED

ENTER

ESC

®

29.

If the burner operation is abnormal, refer to Trouble Shooting Suggestions, as well as

trouble shooting information included in the flame safeguard manufacturer’s bulletin

shipped with the burner. It is also strongly suggested that all test procedures outlined in

the flame safeguard control manufacturer’s bulletin be conducted.

30.

Complete the Burner Start Up Information and Test Data sheets on

page 22.

14.

GAS PILOT IGNITION ADJUSTMENT

Excessive gas pressure and insufficient air are the most common causes of pilot ignition failure.

Gas pressure should be read at the test tee on the pilot gas supply pipe with a manometer or 0

– 10” W.C. gauge. Look for stability of gas pressures at all times. Some job conditions or heat

exchangers may require larger air damper openings or different gas pressures than

recommended. For dependable pilot ignition, always use air damper setting to provide the

MOST air and LOWEST pilot gas pressure settings allowable for good pilot signal at all times.

1.

Remove pilot assembly and check for proper orifice size and spark gap. The spark gap

between the electrode and inside radius of the gas pilot assembly should be 1/8” – 3/32”.

See Figure 11.

FIGURE 7

Typical Pilot

    D)

Element Temperature Safety limit 

Each burner is equipped with an RKC Instrument model SA100L 

temperature controller mounted within the burner control panel. The 

controller is attached to a thermocouple mounted on the inside of the 

fiber matrix element.  Some models have a second temperature 

controller which attaches to an infrared thermocouple.  This infrared 

thermocouple senses the temperature inside the fiber matrix element.  

The controller is a safety device designed to shut down the burner if 

the internal temperature exceeds 350 degrees F.

The controller has two digital readouts.  The upper number represents  

the current temperature at the thermocouple.  The lower number 

represents the setpoint.  The start-up technician must ensure the 

factory setpoint of 350 degrees F is correctly set. If not, the setting can 

be adjusted by pressing the Set button.  At this time the first digit of the 

setpoint field will flash.  The setpoint can be adjusted by pressing the 

up or down buttons as needed to select 350 degrees.  Press Set three  

times to return the display to the main screen which shows the current 

temperature over the setpoint.  Press the Reset button.  The setpoint is 

now reset to the new value.

This device is an integral safety limit of the burner do not 

disconnect or change the setting above the factory setting. 

2)

Disconnect both wires at the air flow switch and temporarily clip them

together. Make sure that they cannot ground against anything, since they

will be powered with 110 volts during the test.

3)

Put a continuity meter across the common and normally open terminals

on the air switch.

4)

Close the gas train checking cock.

5)

Start the blower motor. The meter should read electrical continuity as

soon as the blower starts.

6)

Disconnect the wire which energizes coil of blower motor relay (starter),

or open the main power disconnect switch to the burner. Within 3 to 4

seconds after the blower motor is de-energized, the meter should indicate

an open air flow switch circuit (no continuity).

7)

If the switch does not open in 3 to 4 seconds, re-adjust accordingly. Turn

the air flow switch adjustment screw clockwise to shorten cut-off response

time and counter-clock-wise to lengthen cut-off response time.

8)

Turn the burner power off. Remove the shorting clip from the two

disconnected wires, cover them with electrical tape and let them hang loose

(they will be powered with 110 volts, so don’t let them ground out).

9)

Open the gas train checking cock. Turn the burner on. With the wires

disconnected, the burner should go into a purge cycle, although neither

the ignition nor the main fuel valve circuits will be energized. If they do

energize, there is a wiring problem. Correct as required.

10)

Turn power off. Reconnect the air flow switch wires to the air flow switch

terminals. Place burner back into normal operation.

28.

The Owner’s Operating Instructions,

page 26  

of this manual, should be posted in a

clearly visible location close to the burner.

12

NOVA PLUS Installation & Operation Manual - 

POWER FLAME INCORPORATED

DC4 DRAFT CONTROL

ENTER

ESC

®

10. Re-start the burner. With the pilot gas cock closed, the burner will go through a blower

pre-purge period, after which the gas pilot ignition transformer will be energized, although

no pilot will be established. (At no time should there be any flame signal reading, nor

should the main gas valve attempt to open.) At the end of the pilot trial for ignition and

blower purge period, the flame safeguard control should shut the system down in a safety

lockout mode, requiring manual reset of the flame safeguard control to restart the burner.

11. Wait three minutes, reset the flame safeguard control safety switch (restarting the burner)

and open the pilot gas cock. When the blower pre-purge period ends and the burner is

energized – if the flame safeguard control has a test/run switch – flip the switch to the test

position while the pilot is on and make adjustments as required.

See pages 15 & 16 

for pilot

ignition adjustments. Recycle the burner several times to make certain pilot operation is

reliable.

12. With pilot adjustments completed, reset the switch to the Run position, which will allow the

sequence to proceed to the automatic gas valve energizing position.

13. When the main automatic gas valve begins to open, slowly open the checking gas cock to

light off the main flame. The main flame should light immediately. If not, it may be

necessary to eliminate air from the main gas line and/or adjust main gas pressure

regulator flow rates.

14. Adjust the burner as necessary to provide smooth ignition of the main flame. If the flame

signal drops significantly when the main automatic gas valve opens, slightly increase the

pilot gas pressure to attain a stable flame signal value.

15.

Refer to item 27, page 13, 

carefully for recommended limit control and other control devices

operational checkout.

16. Initial adjustments should be made at the low fire position. All Power Flame burners are

factory tested and adjusted. However, to determine that the metering butterfly valve is, in

fact, in the low fire position, observe the end of the metering valve shaft. The slot in the

end of the shaft indicates the position of the valve. When the slot is in the horizontal

position (parallel with the gas flow direction), the valve is fully open. On servo operated

systems, verify the valve position by viewing through the end of the pipe.

17. Tighten (finger tight) the hex bolt to the linkage rod at the swivel on the modulating motor

driver arms and run the motor through its full travel to ensure that the linkage is free and

that limits on the metering device and air dampers are not exceeded.

18. Turn the burner on and let it advance to the main flame light off position. Take action as

necessary to hold the linkage at the low fire position by using a manual potentiometer or

electrically disconnecting the modulating motor. Power Flame burners are tested at the

factory and linkage adjustments for modulation are made at that time.

19. With the burner in the factory set low fire position, (verify by checking mixing spool air

pressure of typically 0.2” to 0.5”) adjust air and fuel linkage to good fuel/air ratio low fire

settings (6 – 9% O

2

little or no CO). Mark the linkage at the new settings.

20. Increase the firing rate to the midway point. Set the fuel/air ratios to achieve good

combustion values (6 - 9% O

2

little or no CO). Mark the linkage as a reference point for

this new mid fire position.

Summary of Contents for Nova Plus

Page 1: ...Copyright 2006 Power Flame Incorporated Printed in U S A Power F 4 DRAFT CONTROL ENTER ESC Power Flame Incorporated Power Flame Incorporated Nova Plus Nova Plus Installation and Operation Manual Installation and Operation Manual ...

Page 2: ...witches 3 Extinguish any open flame 4 Call your gas supplier immediately NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC Cmax Installation Operation Manual POWER FLAME INCORPORATED 2 P PO OW WE ER R F FL LA AM ME E M MO OD DE EL L C Cm ma ax x B BU UR RN NE ER R...

Page 3: ...s 6 9 Burner Mounting General 6 10 Combustion Chamber General 7 11 General Start Up Procedures 8 12 Burner Start Up and Service Test Equipment Required 10 13 Burner Start Up Sequence Instructions 10 14 Gas Pilot Ignition Adjustment 15 15 Trouble Shooting Suggestions 16 16 Maintenance 19 17 Burner Startup Information Test Data 22 18 Owner Operating Instructions 26 NOVA PLUS Installation Operation M...

Page 4: ... with recommendations of Underwriters Laboratories Inc and The National Electrical Code Components are wired to numbered terminal strips Panel and burners are factory fire tested before shipment Comprehensive wiring and gas piping diagrams are furnished with each burner in accordance with individual job or application requirements Wall mounted or free standing control panels are also available 1 2...

Page 5: ...ervice Department in Parsons Kansas or you may register on line through the Power Flame website www powerflame com All communications with the factory will be handled more efficiently if the burner is identified by the burner model serial and job numbers This information is stamped into the burner nameplate that is attached to the integral control panel or to the burner when remote control panels ...

Page 6: ...________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ ________________...

Page 7: ..._____________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ ______________________________________________________...

Page 8: ...______________________ Name of Technician Performing Start Up______________________________________________________________________ Type of Gas Natural LP Other __________________________ Gas Firing Gas Pressure at Train Inlet Flame signal Readings Stack Outlet Test Point Draft Burner in Off Position ________ W C Pilot________________________ Low Fire ____________________ Low Fire ________________...

Page 9: ...ket or non asbestos high temperature rope packing to prevent any products of combustion from escaping from the combustion chamber through the burner boiler mounting flanges The burner assembly must be supported at the base of the housing to prevent undue strain on the front plate A mounting pedestal is furnished for this purpose 21 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED D...

Page 10: ...uctions Low draft fan air pressure Monthly Operator Refer to this manual and control manufacturer s and damper instructions High low gas pressure interlocks Monthly Operator Refer to instructions in this manual Fuel valve interlock switch Annually Service Technician Refer to valve manufacturer s instructions Purge switch Annually Service Technician Refer to fuel air control motor manufacturer s in...

Page 11: ...tart Up A thoroughly qualified burner technician must be employed to provide the initial burner start up as well as any subsequent servicing of the burner and related controls A representative of the owner and or the person or persons responsible for operating and maintaining the unit should be present during the initial start up A service representative may also be required by the local utility o...

Page 12: ...or atmospheric vent line obstructed Correct G Defective main gas pressure regulator replace Misadjusted main gas pressure regulator readjust to meet required operational values 5 Carbon Monoxide Readings Too High A Flame impingement on cold heat transfer surfaces caused by excessive firing rate Reduce firing rate to correct input volume B Flame impingement on cold combustion chamber surfaces due t...

Page 13: ... when main flame lights the air flow switch is not so critically set as to allow occasional momentary opening of the air switch contacts 10 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC 12 BURNER START UP AND SERVICE TEST EQUIPMENT REQUIRED The following test equipment is required to ensure proper start up and adjustment of burner equipment to obtain ...

Page 14: ...e operating condition Secondary causes lockout Set to actuate at approximately 0 7 w c under normal operating conditions Verify acceptable 02 level Combustion Air Flow Switch 16 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC Table 3 Acceptable Stable Pilot and or Main Flame Current Readings Control U V Infrared R7800 1 25 5 0 DC Volts 1 25 5 0 DC Volts...

Page 15: ...e burner on With the wires disconnected the burner should go into a purge cycle although neither the ignition nor the main fuel valve circuits will be energized If they do energize there is a wiring problem Correct as required 10 Turn power off Reconnect the air flow switch wires to the air flow switch terminals Place burner back into normal operation 28 The Owner s Operating Instructions page 26 ...

Page 16: ...ches as follows a Low gas pressure switch With the burner running slowly close the main gas train manual shutoff cock and adjust the switch to open its circuit when the pressure falls to a maximum of 50 below its normal value The burner will shut down Open the 14 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC manual gas shutoff cock to the full open po...

Page 17: ...ches as follows a Low gas pressure switch With the burner running slowly close the main gas train manual shutoff cock and adjust the switch to open its circuit when the pressure falls to a maximum of 50 below its normal value The burner will shut down Open the 14 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC manual gas shutoff cock to the full open po...

Page 18: ...e burner on With the wires disconnected the burner should go into a purge cycle although neither the ignition nor the main fuel valve circuits will be energized If they do energize there is a wiring problem Correct as required 10 Turn power off Reconnect the air flow switch wires to the air flow switch terminals Place burner back into normal operation 28 The Owner s Operating Instructions page 26 ...

Page 19: ...e operating condition Secondary causes lockout Set to actuate at approximately 0 7 w c under normal operating conditions Verify acceptable 02 level Combustion Air Flow Switch 16 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC Table 3 Acceptable Stable Pilot and or Main Flame Current Readings Control U V Infrared R7800 1 25 5 0 DC Volts 1 25 5 0 DC Volts...

Page 20: ... when main flame lights the air flow switch is not so critically set as to allow occasional momentary opening of the air switch contacts 10 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC 12 BURNER START UP AND SERVICE TEST EQUIPMENT REQUIRED The following test equipment is required to ensure proper start up and adjustment of burner equipment to obtain ...

Page 21: ...or atmospheric vent line obstructed Correct G Defective main gas pressure regulator replace Misadjusted main gas pressure regulator readjust to meet required operational values 5 Carbon Monoxide Readings Too High A Flame impingement on cold heat transfer surfaces caused by excessive firing rate Reduce firing rate to correct input volume B Flame impingement on cold combustion chamber surfaces due t...

Page 22: ...tart Up A thoroughly qualified burner technician must be employed to provide the initial burner start up as well as any subsequent servicing of the burner and related controls A representative of the owner and or the person or persons responsible for operating and maintaining the unit should be present during the initial start up A service representative may also be required by the local utility o...

Page 23: ...uctions Low draft fan air pressure Monthly Operator Refer to this manual and control manufacturer s and damper instructions High low gas pressure interlocks Monthly Operator Refer to instructions in this manual Fuel valve interlock switch Annually Service Technician Refer to valve manufacturer s instructions Purge switch Annually Service Technician Refer to fuel air control motor manufacturer s in...

Page 24: ...ket or non asbestos high temperature rope packing to prevent any products of combustion from escaping from the combustion chamber through the burner boiler mounting flanges The burner assembly must be supported at the base of the housing to prevent undue strain on the front plate A mounting pedestal is furnished for this purpose 21 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED D...

Page 25: ...______________________ Name of Technician Performing Start Up______________________________________________________________________ Type of Gas Natural LP Other __________________________ Gas Firing Gas Pressure at Train Inlet Flame signal Readings Stack Outlet Test Point Draft Burner in Off Position ________ W C Pilot________________________ Low Fire ____________________ Low Fire ________________...

Page 26: ..._____________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ ______________________________________________________...

Page 27: ...________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ ________________...

Page 28: ...ervice Department in Parsons Kansas or you may register on line through the Power Flame website www powerflame com All communications with the factory will be handled more efficiently if the burner is identified by the burner model serial and job numbers This information is stamped into the burner nameplate that is attached to the integral control panel or to the burner when remote control panels ...

Page 29: ... with recommendations of Underwriters Laboratories Inc and The National Electrical Code Components are wired to numbered terminal strips Panel and burners are factory fire tested before shipment Comprehensive wiring and gas piping diagrams are furnished with each burner in accordance with individual job or application requirements Wall mounted or free standing control panels are also available 1 2...

Page 30: ... 3 Extinguish any open flame 4 Call your gas supplier immediately NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC Cmax Installation Operation Manual POWER FLAME INCORPORATED 2 P PO OW WE ER R F FL LA AM ME E M MO OD DE EL L C Cm ma ax x B BU UR RN NE ER R For us...

Page 31: ...er Flame Incorporated Power Flame Incorporated Nova Plus Nova Plus Installation and Operation Manual Installation and Operation Manual Power Flame Incorporated 2001 South 21st Street Parsons KS 67357 Telephone 620 421 0480 FAX 620 421 0948 Product Support 620 820 8301 Website http www powerflame com e mail CSD powerflame com ...

Reviews: