background image

17

NOVA PLUS Installation & Operation Manual - 

POWER FLAME INCORPORATED

DC4 DRAFT CONTROL

ENTER

ESC

®

E.

Occasional low voltage supply. Have local utility correct. Make certain that the

burner control circuit transformer (if supplied) is correct for the voltage being

supplied.

F.

Occasional low gas supply pressure. Have utility correct.

G.

Element air pressure switch opens during purge. Reset switch to remain closed

just under maximum purge pressure.

3.

Burner Motor Runs, but Pilot Does Not Light

A.

Gas supply to burner shut off – make sure all manual gas supply valves are

open. Automatic high pressure valve at meter such as Sentry type tripped shut

due to high gas pressure – reset valve and correct cause for trip out.

B.

Pilot solenoid valve not opening – listen and feel for valve actuation. Solenoid

valve not being powered – check electrical circuitry. Replace coil or entire valve

if coil is burned out.

C.

Defective gas pilot regulator – replace.

D.

Gas pressure too high or too low at pilot orifice. Check orifice size in gas pilot

assembly. Replace if incorrect. Refer to gas pilot adjustments for correct

settings. Readjust as required.

E.

Defective ignition transformer – replace. Incorrect ignition electrode settings –

refer to gas pilot adjustments for correct settings.

F.

Defective flame safeguard control or plug in purge timing card. Replace as

required.

G.

Air flow switch not making circuit – check out electrically and correct pressure

adjustment on switch, if required. Defective air flow switch – replace. Air switch

negative pressure sensing tube out of position – reposition as necessary.

4.

Burner Motor Runs and Pilot Lights, but Main Gas Flame Is Not Established

A.

Main shutoff or test cock closed. Check to make certain fully open.

B.

Pilot flame signal reading too low to pull in flame safeguard relay. Refer to gas

pilot settings section and readjust as required.

C.

Defective automatic main or auxiliary gas shut off valves. Check electrical

circuitry to valves. Replace valves or correct circuitry as required.

D.

Defective flame safeguard control or plug in amplifier. Check and replace as

required.

E.

Butterfly valve set incorrectly on modulating burner. Readjust as required.

Table 3

Acceptable Stable Pilot and/or Main Flame Current Readings

Control

U.V.

Infrared

R7800

1.25-5.0 DC Volts

1.25-5.0 DC Volts

E

MK7 

5 min., 10 or greater normal 

5 min., 10 or greater normal

110

10 min., 20 or greater normal

10 min., 20 or greater normal

15.

TROUBLE SHOOTING SUGGESTIONS

1.

Burner Fails to Start

A.

Defective On/Off or fuel transfer switch. Replace

B.

Control circuit has an open control contact. Check limits, low water cutoff, proof

of closure switch and others as applicable.

C.

Bad fuse or switch open on in-coming power source. Correct as required.

D.

Motor overloads tripped. Reset and correct cause for trip out.

E.

Flame safeguard control safety switch tripped out. Reset and determine cause

for apparent flame failure.

F.

Loose connections or faulty wiring. Tighten all terminal screws and consult

wiring diagram furnished with the burner.

G.

Flame safeguard control starting circuit blocked due to flame relay being

energized. Possible defective scanner – replace. Possible defective amplifier –

replace. Scanner actually sighting flame due to leaking fuel valve – correct

unwanted flame cause. Defective flame safeguard control – replace.

H.

Defective blower motor. Repair or replace.

I.

LFI air switch open. Verify damper is in the low fire position or reset switch.

2.

Occasional Lockouts For No Apparent Reason

A.

Gas pilot ignition failure. Refer to pilot adjustment section and readjust to make

certain that the ignition is instant and that flame signal readings are stable and

above minimum values. Use a manometer or 0 to 10” W.C. gas pressure gauge

on pilot test tee to make certain that pressure is as recommended.

B.

Gas pilot ignition. Verify that there are no cracks in the porcelain and that

transformer end and electrode end plug in connections are tight.

C.

Loose or broken wires. Check all wire nut connections and tighten all terminal

screw connections in panel and elsewhere as appropriate.

D.

Ensure that when main flame lights, the air flow switch is not so critically set as to

allow occasional momentary opening of the air switch contacts.

10

NOVA PLUS Installation & Operation Manual - 

POWER FLAME INCORPORATED

DC4 DRAFT CONTROL

ENTER

ESC

®

12. BURNER START UP AND SERVICE TEST EQUIPMENT REQUIRED

The following test equipment is required to ensure proper start up and adjustment of burner

equipment to obtain maximum efficiency and reliability of operation.

For any Gas

Flue Gas Analyzer with O

2

,

NOx, CO capability (Required)

Stack thermometer

Draft gauge or inclined

Manometer

Combination volt/ammeter

D.C. microammeter or D.C.

U-Tube manometer 0-16”

W.C. or calibrated 0-10” and

0-35” W.C. pressure gauges.

PSIG 0-5#

(Higher pressure ranges may

be necessary depending upon

gas inlet supply pressure)

Voltmeter, as required by

Flame safeguard

Measure the excess O

2

and test for CO to make certain that the burner is adjusted so that it has an

excess 0

2

of typically 6% to 9% when firing without FGR (flue gas recirculation). The excess 0

2

level

when using FGR will typically be 5% to 7%. This is the typical excess O

2

range required for the premix

burner to obtain reduced NOx emissions. If higher excess O

2

is required to obtain a particular emission

level the CO level must be checked thoroughly. CO is a dangerous product of incomplete combustion

and is associated with combustion inefficiency and increased fuel cost. Any CO readings on any fuel

should be near 0% or less than 50 ppm.

13.

BURNER START UP SEQUENCE INSTRUCTIONS

1.

Prior to burner start up – contact the local gas company to determine if any correction

factors have to be applied to their indicated meter flow rates. This information is important

as relates to achieving specific heat exchanger BTU/HR inputs.

Refer to Figure 2, page 4

and the burner rating plate for additional firing rate information.

2.

Refer to

Figure 6, page 11 

for air switch locations and pressure settings.

3.

Refer to the gas piping diagram furnished with the burner. Check gas piping, controls and

valves for leaks and compliance with codes.

4.

Check all linkages and servo couplings for proper position and tightness

5.

Close main checking and pilot gas cocks. Install one gas pressure gauge on the manifold

(orifice tee) to read burner firing head pressure (use 0-32” W.C. gauge or a manometer).

Install a second gas pressure gauge to read gas supply pressure between the main gas

cock and the inlet to the main gas pressure regulator (use a 0-5 psi gauge or as

appropriate). If there is no tapping in this location, install a tee at the point where the pilot

gas supply is connected to the main gas line. Slowly open the main gas cock in order to

determine that the incoming gas pressure is within the specified limits of the main and pilot

gas pressure regulators, automatic fuel valves and gas pressure switches.

Summary of Contents for Nova Plus

Page 1: ...Copyright 2006 Power Flame Incorporated Printed in U S A Power F 4 DRAFT CONTROL ENTER ESC Power Flame Incorporated Power Flame Incorporated Nova Plus Nova Plus Installation and Operation Manual Installation and Operation Manual ...

Page 2: ...witches 3 Extinguish any open flame 4 Call your gas supplier immediately NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC Cmax Installation Operation Manual POWER FLAME INCORPORATED 2 P PO OW WE ER R F FL LA AM ME E M MO OD DE EL L C Cm ma ax x B BU UR RN NE ER R...

Page 3: ...s 6 9 Burner Mounting General 6 10 Combustion Chamber General 7 11 General Start Up Procedures 8 12 Burner Start Up and Service Test Equipment Required 10 13 Burner Start Up Sequence Instructions 10 14 Gas Pilot Ignition Adjustment 15 15 Trouble Shooting Suggestions 16 16 Maintenance 19 17 Burner Startup Information Test Data 22 18 Owner Operating Instructions 26 NOVA PLUS Installation Operation M...

Page 4: ... with recommendations of Underwriters Laboratories Inc and The National Electrical Code Components are wired to numbered terminal strips Panel and burners are factory fire tested before shipment Comprehensive wiring and gas piping diagrams are furnished with each burner in accordance with individual job or application requirements Wall mounted or free standing control panels are also available 1 2...

Page 5: ...ervice Department in Parsons Kansas or you may register on line through the Power Flame website www powerflame com All communications with the factory will be handled more efficiently if the burner is identified by the burner model serial and job numbers This information is stamped into the burner nameplate that is attached to the integral control panel or to the burner when remote control panels ...

Page 6: ...________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ ________________...

Page 7: ..._____________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ ______________________________________________________...

Page 8: ...______________________ Name of Technician Performing Start Up______________________________________________________________________ Type of Gas Natural LP Other __________________________ Gas Firing Gas Pressure at Train Inlet Flame signal Readings Stack Outlet Test Point Draft Burner in Off Position ________ W C Pilot________________________ Low Fire ____________________ Low Fire ________________...

Page 9: ...ket or non asbestos high temperature rope packing to prevent any products of combustion from escaping from the combustion chamber through the burner boiler mounting flanges The burner assembly must be supported at the base of the housing to prevent undue strain on the front plate A mounting pedestal is furnished for this purpose 21 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED D...

Page 10: ...uctions Low draft fan air pressure Monthly Operator Refer to this manual and control manufacturer s and damper instructions High low gas pressure interlocks Monthly Operator Refer to instructions in this manual Fuel valve interlock switch Annually Service Technician Refer to valve manufacturer s instructions Purge switch Annually Service Technician Refer to fuel air control motor manufacturer s in...

Page 11: ...tart Up A thoroughly qualified burner technician must be employed to provide the initial burner start up as well as any subsequent servicing of the burner and related controls A representative of the owner and or the person or persons responsible for operating and maintaining the unit should be present during the initial start up A service representative may also be required by the local utility o...

Page 12: ...or atmospheric vent line obstructed Correct G Defective main gas pressure regulator replace Misadjusted main gas pressure regulator readjust to meet required operational values 5 Carbon Monoxide Readings Too High A Flame impingement on cold heat transfer surfaces caused by excessive firing rate Reduce firing rate to correct input volume B Flame impingement on cold combustion chamber surfaces due t...

Page 13: ... when main flame lights the air flow switch is not so critically set as to allow occasional momentary opening of the air switch contacts 10 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC 12 BURNER START UP AND SERVICE TEST EQUIPMENT REQUIRED The following test equipment is required to ensure proper start up and adjustment of burner equipment to obtain ...

Page 14: ...e operating condition Secondary causes lockout Set to actuate at approximately 0 7 w c under normal operating conditions Verify acceptable 02 level Combustion Air Flow Switch 16 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC Table 3 Acceptable Stable Pilot and or Main Flame Current Readings Control U V Infrared R7800 1 25 5 0 DC Volts 1 25 5 0 DC Volts...

Page 15: ...e burner on With the wires disconnected the burner should go into a purge cycle although neither the ignition nor the main fuel valve circuits will be energized If they do energize there is a wiring problem Correct as required 10 Turn power off Reconnect the air flow switch wires to the air flow switch terminals Place burner back into normal operation 28 The Owner s Operating Instructions page 26 ...

Page 16: ...ches as follows a Low gas pressure switch With the burner running slowly close the main gas train manual shutoff cock and adjust the switch to open its circuit when the pressure falls to a maximum of 50 below its normal value The burner will shut down Open the 14 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC manual gas shutoff cock to the full open po...

Page 17: ...ches as follows a Low gas pressure switch With the burner running slowly close the main gas train manual shutoff cock and adjust the switch to open its circuit when the pressure falls to a maximum of 50 below its normal value The burner will shut down Open the 14 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC manual gas shutoff cock to the full open po...

Page 18: ...e burner on With the wires disconnected the burner should go into a purge cycle although neither the ignition nor the main fuel valve circuits will be energized If they do energize there is a wiring problem Correct as required 10 Turn power off Reconnect the air flow switch wires to the air flow switch terminals Place burner back into normal operation 28 The Owner s Operating Instructions page 26 ...

Page 19: ...e operating condition Secondary causes lockout Set to actuate at approximately 0 7 w c under normal operating conditions Verify acceptable 02 level Combustion Air Flow Switch 16 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC Table 3 Acceptable Stable Pilot and or Main Flame Current Readings Control U V Infrared R7800 1 25 5 0 DC Volts 1 25 5 0 DC Volts...

Page 20: ... when main flame lights the air flow switch is not so critically set as to allow occasional momentary opening of the air switch contacts 10 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC 12 BURNER START UP AND SERVICE TEST EQUIPMENT REQUIRED The following test equipment is required to ensure proper start up and adjustment of burner equipment to obtain ...

Page 21: ...or atmospheric vent line obstructed Correct G Defective main gas pressure regulator replace Misadjusted main gas pressure regulator readjust to meet required operational values 5 Carbon Monoxide Readings Too High A Flame impingement on cold heat transfer surfaces caused by excessive firing rate Reduce firing rate to correct input volume B Flame impingement on cold combustion chamber surfaces due t...

Page 22: ...tart Up A thoroughly qualified burner technician must be employed to provide the initial burner start up as well as any subsequent servicing of the burner and related controls A representative of the owner and or the person or persons responsible for operating and maintaining the unit should be present during the initial start up A service representative may also be required by the local utility o...

Page 23: ...uctions Low draft fan air pressure Monthly Operator Refer to this manual and control manufacturer s and damper instructions High low gas pressure interlocks Monthly Operator Refer to instructions in this manual Fuel valve interlock switch Annually Service Technician Refer to valve manufacturer s instructions Purge switch Annually Service Technician Refer to fuel air control motor manufacturer s in...

Page 24: ...ket or non asbestos high temperature rope packing to prevent any products of combustion from escaping from the combustion chamber through the burner boiler mounting flanges The burner assembly must be supported at the base of the housing to prevent undue strain on the front plate A mounting pedestal is furnished for this purpose 21 NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED D...

Page 25: ...______________________ Name of Technician Performing Start Up______________________________________________________________________ Type of Gas Natural LP Other __________________________ Gas Firing Gas Pressure at Train Inlet Flame signal Readings Stack Outlet Test Point Draft Burner in Off Position ________ W C Pilot________________________ Low Fire ____________________ Low Fire ________________...

Page 26: ..._____________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ ______________________________________________________...

Page 27: ...________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ ________________...

Page 28: ...ervice Department in Parsons Kansas or you may register on line through the Power Flame website www powerflame com All communications with the factory will be handled more efficiently if the burner is identified by the burner model serial and job numbers This information is stamped into the burner nameplate that is attached to the integral control panel or to the burner when remote control panels ...

Page 29: ... with recommendations of Underwriters Laboratories Inc and The National Electrical Code Components are wired to numbered terminal strips Panel and burners are factory fire tested before shipment Comprehensive wiring and gas piping diagrams are furnished with each burner in accordance with individual job or application requirements Wall mounted or free standing control panels are also available 1 2...

Page 30: ... 3 Extinguish any open flame 4 Call your gas supplier immediately NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC NOVA PLUS Installation Operation Manual POWER FLAME INCORPORATED DC4 DRAFT CONTROL ENTER ESC Cmax Installation Operation Manual POWER FLAME INCORPORATED 2 P PO OW WE ER R F FL LA AM ME E M MO OD DE EL L C Cm ma ax x B BU UR RN NE ER R For us...

Page 31: ...er Flame Incorporated Power Flame Incorporated Nova Plus Nova Plus Installation and Operation Manual Installation and Operation Manual Power Flame Incorporated 2001 South 21st Street Parsons KS 67357 Telephone 620 421 0480 FAX 620 421 0948 Product Support 620 820 8301 Website http www powerflame com e mail CSD powerflame com ...

Reviews: