Dimensions ( mm )

Weight (Kg)

SE-4E

1

1

0

MODEL

 

GENERAL DESCRIPTION

TECHNICAL SPECIFICATION

Length 

Height 

Width

DESIGN AND MANUFACTURE
BY

RESEARCH

 

TEAM 

OF

POWER

 

ELECTRONICS  C

.

O.

       GREECE

ADJUSTMENTS

STAB

 

for stability voltage control

VOLT 

for voltage output level

FINE POT

   for external  voltage  level

for power factor correction 

P/F

 

U/F

 

for

 under frequency protection

 

INPUT 350 - 500 V

OUTPUT 0 - 1

5

0 V DC

CURRENT 

A

120  CONTINUOUS

EXC.FIELD 1 Ohm MIN

REGULATION  +/-  1%

OPER.TEMP +

8

MAX

FREQ.  40 - 70 Hz 

MANUAL OR

AUTOMATIC FLASH

ADJUSTABLE UNDER

FREQUENCY

 PROTECTION

QUADRATURE DROOP
FOR PARALLED OPERATION

AUTOMATIC 
GOOD CABLE-CONNECTION 
INSPECTION SYSTEM 

The  

SE

-4

E

110

 is a high performance 

t

hree angle fullwave phase AVR

 designed to  

performs especially good for high current brush 
generators.It powerered from a special 
transformer that isolates it at the same time.

180

420

460

16

3 PHASE

 

 

ONLY

OF NEUTRAL 

NO USE 

   

Length 

Height 

Width

CT =

MAX AMPERES

5 AMPERES

IMPORTANT  INSTALLATION  NOTES 

MODEL  SE-4E

110

THE CLOCKWISE TURNING
OF U/S TRIMMER 
ACTIVATES THIS FEATURE AT
HIGHER Hz.  (~74Hz THE HIGHEST) 

25 TURNS TRIMMER   (IT DOES NOT STOP)

THE ANTI-CLOCKWISE TURNING
OF U/S TRIMMER 
ACTIVATES THIS FEATURE AT
LOWER Hz.(~22Hz THE LOWEST)

THE ORANGE NEON INDICATOR IS LIT WHEN:

 

   

                         

THE PHASE SEQUENCE ARE 

WRONG.

THE GREEN LED IS LIT WHEN:

 

THE IDENTITY OF THE PHASES ARE OK.
THE SEQUENCE OF THE PHASES ARE OK. 
THE POLARITY OF CURRENT TRANSFORMER  ARE OK.

                            

THE CIRCUIT OF THIS LED WILL ACTIVATED ONLY IF:       

                     

A:  THE CT IS INSTALLED.     

  

                                   

B:  THE GENERATOR IS UNDER LOAD.

STABILITY 

E-D close:

30% 

stability (default).

E-F  close:  

6

0% stability.

no jumper:            

100% 

stability.

F
E
D

F
E
D

F
E
D

SPECIFICATION

OUTPUT

INPUT

VOLT AC
PHASE
FREQUENCY

VOLT DC
CURRENT
EXC. FIELD OHMS

0V - 150V 

120A CONTINUOUS

 1 Ohm MINIMUM

350-500

NO NEUTRAL

40 - 70 Hz

OPERATIONAL TEMPERATURE  80 C MAX

AUTOMATIC FLASH

REGULATION   +/- 0.5%

WRONG 

PHASE SEQUENCE INDICATOR.

CABLE CHECKER IN PARALLEL OPERATION

.

P/F COMPENSATED IN PARALLEL OPERATION.

UNDER FREQUENCY PROTECTION.

50 - 60 Hz COMPATIBILITY.

USE MAX 32 AMPERES FUSES.

CONNECT FINE VOLTAGE POT ON PANEL (500 Ohm) 

                     

OR ELSE YOU MUST LINK TERMINAL s’ - t’.

IN CASE OF USING 

"

CURRENT TRANSFORMER                           

CT

      

     

IT MUST BE TO PHASE V.

FUSES BOX

32A

32A

32A

    BRUSH
GENERATOR

SWITCH

ACB

MAIN

l

k

L

K

380 - 440 V BUS  BAR

J

K

J

K

X Y Z

U V W

s' t'

CT

U

W

V

  FLASH BUTTON

    

 FOR

OR LINK

AUTOMATIC FLASH

FINE VOLTAGE

POT 500 Ohm

OR LINK s’ - t’ 

A B

R

S

T

l

k

2

2.5mm

2

10mm

2

25mm

POWER & ISOLATION

TRANSFORMER

X Y Z

W

V

U

2

1.5mm

  WRONG PHASE SEQUENCE  

  INDICATOR

Cable checker.

Lit when all cable 
connections are good.

Under Frequency 
protection checker

.

Lit when U/Hz
protection is activated.

UNDER SPEED

F

E

D

STABILITY

-

+

POWER FACTOR

-

+

VOLTAGE

FOR EXCLUSIVE SINGLE OPERATION
THE USE OF 

"

"

 IS 

 

NECESSARY.

CT

NOT

POSITIVE

NEGATIVE

EXCITER

FIELD

2

50mm

UNDER FREQUENCY PROTECTION