background image

ELECTRONICS 

OWER

 

P

 

 

INSTRUCTIONS  TO  INSTALLING 

AND  ADJUSTING  THE  AVR 

 

www.powerelectronics.gr 

 

 

[email protected]

 

 

 

 

 

 

MODELS:  

   SE-4A15,   SE-4E15,   SE-4A65,   SE-4E65,   SE-3A110, SE-3E110 

 

 SE-4E110, SE-4A110, SE-4E150, SE-4A150, SE-4E200, SE-4A200 

 

 

U/S - 

Under Frequency Protection.

 It protects the generator from over-excitation current due to lower engine revs.  

To adjusting the U/S trimmer proceed as follows

 

The AVR comes with pre-configured 

Under Frequency 

protection. 

If re-adjusting is to be needed, proceed to the follows: 

 

1.  

Turn anti-clockwise the 

U/S

 

trimmer all the way 

(25 turns). 

2.

  Start the engine and wait until voltage is built up. 

3.  

Reduce the fuel from the Governor until the periods are 

6 Hz

       

     less than the normal. (e.g. If the engine is running on 

50Hz

,  

     then the periods are to be reduced to 

44Hz

  

     and if the engine is running on 

60Hz

, then the periods  

     are to be reduced to 

54 Hz.   

4.

  Turn clockwise the 

U/S

 

trimmer until the 

red led

  

 

     (which is located behind the 

VOLT 

trimmer) lights up. 

     (

Note that the generator voltage will also starts to drop). 

5.

  Restore generator to the normal state 

(50 or 60 Hz).

 

 

STAB 

- Stability.

 

It eliminates the voltage fluctuations. 

To adjusting the STAB trimmer, proceed as follows

 

On the left side of the central processing PCB, 

three pins can be found. Depending on which pins 

we decide to short-circuit, different levels of stability 

can be achieved. 

There are three specific options. 

These are: 30%, 60% and 100% over the whole of  

the stability curve. It can also be observed 

diagrammatically on the image provided to the right -------> 

 

 

VOLT - 

Voltage.

 Voltage adjustment. It co-operates with the external pot. 

To adjusting the VOLT trimmer, proceed as follows:

 

 

Since the engine has the right-periods (cycles), then the remote knob is adjusted to the middle position. 

Then the 

VOLT 

trimmer (which is located in the main unit) is adjusted until the right voltage is reached. 

All the above adjustments i.e. 

U/S, STAB, VOLT

, must be done without any load in the generator, 

the switch 

(ACB) 

must be in 

OFF 

position. 

 

P/F 

- Power Factor

. This adjustment is done when the generator is already in parallel with another or others. 

To adjusting the P/F trimmer proceed as follows:

 

 

We start by placing the trimmer to the middle position. 

If turning it anti-clockwise, the amperes of generator build-up in relation to the other generator. 

If the trimmer is moved in a clockwise manner, the amperes are reduced in relation to the other or others generators

 

GREEN LED CABLE CHECKER. 

The green led will help to achieve the right installation. 

 

The green led (which is located behind the 

P/F 

trimmer), will help to achieve the right installation. 

It will light 

only*

 

if all the below are ok: 

 

1.  

The circuit of this led will activated, if only if a current transformer is installed. 

2.  

The generator is 20% at least under load.  

3.

  The identity of the phases is ok. 

4.

  The suggestion of the phases is ok.  

5.

  The polarity of current transformer is ok. 

*If there is more than one wrong cable connection at the same time, there is a chance that the green led will be lighten.

 

25 TURN TRIMMER (IT DOES NOT STOP) 

UNDER FREQ PROTECTION

 

(DEFAULT 

(PRE-ADJUSTED) 

VALUE FOR 380V: 44 Hz 

THE CLOCKWISE TURNING 

OF 

U/S

 TRIMMER ACTIVATES 

THIS FEATURE AT HIGHER Hz. 

(~74Hz THE HIGHEST) 

THE ANTI-CLOCKWISE TURNING 

OF 

U/S

 TRIMMER ACTIVATES 

THIS FEATURE AT LOWER Hz. 

(~22Hz THE LOWEST) 

 

 

(DEFAULT 

(PRE-ADJUSTED) 

VALUE FOR 440V: 54 Hz 

 F 

 F 

 F 

E-D close:     30% stability (default) 

E-F close:      60% stability 

 

No Jumper:  100% stability 

 

Reviews: