POWER ELECTRONICS
SD300 SERIES
POWER CONNECTION
37
Recommended Cable Section
Model
Screw
Torque
[1]
[Kgf * cm / Nm]
Wire
[2]
mm²
AWG
R, S, T
U, V, W
R, S, T
U, V, W
230V 1-phase
0.4 kW
M3.5
(1/8
“)
2.1 ~ 6.1 / 0.2 ~ 0.6
2
2
14
14
0.75 kW
1.5 kW
2.2 kW
M4
(1/8“)
3.5
3.5
12
12
230V 3-phase
0.4 kW
M3.5
(1/8“)
2
2
14
14
0.75 kW
1.5 kW
2.2 kW
3.7 kW
M4
(1/8“)
3.5
3.5
12
12
4 kW
5.5 kW
6
6
10
10
7.5 kW
11 kW
M5
(3/16“)
4.0 ~ 10.2 / 0.4 ~ 1.0
10
10
8
8
15 kW
16
16
6
6
400V 3-phase
0.4 kW
M3.5
(1/8“)
2.1 ~ 6.1 / 0.2 ~ 0.6
2
2
14
14
0.75 kW
1.5 kW
2.2 kW
3.7 kW
M4
(1/8“)
4 kW
5.5 kW
2.5
2.5
14
14
7.5 kW
4
4
12
12
11 kW
M5
(3/16“)
4.0 ~ 10.2 / 0.4 ~ 1.0
15 kW
6
6
10
10
18.5 kW
10
10
8
8
22 kW
[1] Use only the specified torque on the screws, otherwise damage could occur. Loose screws can cause overheating and
damage.
[2]
Wires must permanently support 600V and Tª >75ºC.
Ground Connection
Before connecting the power conductors, make sure that the chassis of the drive and the adjoining cabinets
are connected to ground through the dedicated (PE) terminals. The PE terminals are located in the bottom
part of the drive and labelled with the appropriate ground connection.
Figure 7.10 PE terminals location
Summary of Contents for SD300146
Page 1: ...VARIABLE SPEED DRIVE Variable Speed Drive Hardware and Installation Manual...
Page 2: ......
Page 3: ...Variable Speed Drive Hardware and Installation Manual Edition February 2017 SD30MTHW01CI Rev C...
Page 4: ...SD300 SERIES POWER ELECTRONICS 2 SAFETY SYMBOLS...
Page 62: ...SD300 SERIES POWER ELECTRONICS 60...
Page 65: ...www power electronics com...