Powered by Safety
®
11
01.4IB.46300
Equipment Description
c. r
atings
Refer to the specific job drawings for the detail ratings applicable to a particular controller. The basic
ratings equal or exceed NEMA STD ICS 3, and are summarized in
Table A, Horsepower, Current, and
Table B, Voltage and Interrupting Ratings of Class E2 Medium Voltage Controllers.
Table A Horsepower, Current, and Voltage Ratings
Continuos
Current
(Amperes)
2200-2400V
4000-5000V
6600-7200V
Induction
SYNC
Induction
SYNC
Induction
SYNC
0.8
1.0
0.8
1.0
0.8
1.0
360
1350
1350
1750
2500
2500
3000
4000
4000
5000
720
2500
2500
3500
4500
4500
6000
7000
7000
9500
Table B Voltage and Interrupting Ratings of Class E2 Medium Voltage Controllers
Rated Insulation Voltage
Class E2-AR® Interrupting Rating (Fused)
Maximum Volts, rms
Amperes (rms) Symmetrical
2500
50000
5000
50000
7200
50000
Note:
For additional vacuum contactor ratings information refer to Eaton Technical Data
TD02003001E.
F. M
eDiuM
v
oltage
c
ontactors
Two types of medium voltage vacuum
contactors employed in FlexTrol
™
are the Eaton
and the Eaton Type SL
800A
. Each vacuum contactor has a
feature that is designed to close and interrupt
the AC power circuit under normal conditions
or to interrupt the circuit under overload
emergency conditions. Another feature of
each design is short circuit protection. This
includes current limiting fuses as specified for
the application.
D. B
asic
i
Mpulse
l
evel
The basic impulse level test voltage for motor
control centers rated up to 7.2kV is 45kV. An
optional 60kV voltage level is available with the
addition of a single surge arrestor on each pole
of the main bus per line-up.
e. F
ielD
D
ielectric
t
est
Field Power Frequency Withstand tests are 75%
of (UL 347) requirement of 18.2kV for 7.2kV
equipment. The recommended test voltage is
13.7kV ac rms.