FlexTrol
™
Class E2 Medium Voltage Controllers with
Eaton Contactor
Powered by Safety
®
42
01.4IB.46300
Operation
Table K Eaton Publication References
Storage and Handling
48041
Class E2 Medium Voltage Controllers
Isolating Switch 400A
Isolating Switch 800A
48041
48041
TD02003001E
Medium Voltage Vacuum Contactor
Vacuum Contactor Subassembly
Vacuum Contactor Latch
48041
48041
TD02003001E
Note:
Refer to the most current version of
Eaton literature listed in
.
Figure 22 Blown Fuse Indicator
a
a. Blown Fuse Indicator
6) Power Fuse Inspection
Inspect the condition of all current-limiting
fuses after every fault current condition.
Visually inspect the power fuse blown fuse
indicator
or perform continuity
tests to determine the condition of the
fuses. When visually inspecting a fuse, if the
colored indicator on top of the fuse extends
outwards, the fuse is in the
OPEN
position or
blown. Compare the existing fuse resistance
value to a new fuse value to determine the
condition of the fuse.
Perform continuity tests to determine the
condition of the control power transformer
primary fuses and control power transformer
secondary fuses. Compare the existing
fuse resistance value to a new fuse value
to determine the condition of the fuse. As
required, replace fuses only with new fuses
with the same catalog number, type, voltage
rating, current rating, frequency rating, and
maximum interrupting rating. Refer to the
Operating Instructions
label for complete
instructions on fuse replacement. The
operating instructions label is located on the
inside compartment door of the medium
voltage controller.