15.0 Changing Components
44
© Baxi Heating UK Ltd 2011
15.3
Flowswitch
(Fig. 47)
1. Drain the boiler (see Section 15.1 paragraph 2 & 3).
2. Remove the two screws on the support bracket.
3. Remove the clip securing the flow pipe to the
flowswitch.
4. Disconnect the inline electrical connection.
5. Pull pipe away from flowswitch.
6. Remove the two screws securing the flowswitch to
the boiler.
7. Remove the flowswitch.
8. Fit the new flowswitch and reassemble in reverse
order.
9. Recommission the boiler and check the inhibitor
concentration (see Section 6.2 and 12.1).
Flow Switch
Clip
Flow Pipe
Fig. 47
Support Bracket