TECHNICAL DATA - Page 7
BOILER
SIZE
INJECTOR
SIZE
GAS RATE at
95.0 MJ/m3
(2500 Btu/W)
m3/h (W/h)
INPUT
kW (Btu/h)
OUTPUT
kW (Btu/h)
BURNER
PRESSURE
mbar (in wg)
SUPPLY
PRESSURE
mbar (in wg)
50e
2.2mm
0.73 (25.8)
18.88 (64,400)
15.1 (51,500)
35.7 (14.3)
37 (14.8)
60e
2.4mm
0.89 (31.4)
23.0 (78,500)
18.4 (62,800)
35.7 (14.3)
37 (14.8)
80e
2.7mm
1.13 (40.0)
29.31 (100,000)
23.45 (80,000)
34.1 (13.7)
37 (14.8)
100e
3.0mm
1.42 (50.0)
36.64 (125,000)
29.3 (100,000)
33.2 (13.3)
37 (14.8)
CIRCULATION PUMP SELECTION
The resistance through the heat exchanger when operating
with a water flow rate producing an 11 0C temperature rise
at maximum boiler output are shown in TABLE 2. If other
controls, such as three-position valves are used in the
system, the resistance through them, quoted in their
manufacturer’s literature must be taken into account The
pump may be fitted on either the flow or return and MUST be
wired directly to the boiler terminal block, see FIG. 23. It
must be fitted with two isolating valves which are positioned
as close to the pump as possible. Closing of any valve must
always leave the open vent unobstructed.
TABLE 2
FIG. 5 PRESSURE LOSS ACROSS BOILER
Summary of Contents for PROFILE LPG 100e
Page 4: ...SITE REQUIREMENTS Page 4 FIG 2 GENERAL ARRANGEMENT ...
Page 10: ...TECHNICAL DATA Page 10 FIG 7 FULLY PUMPED SEALED SYSTEM ...
Page 20: ...COMMISSIONING Page 20 FIG 26 FUNCTIONAL FLOW DIAGRAM HONEYWELL FIG 27 BOILER WIRING DIAGRAM ...
Page 23: ......
Page 25: ......
Page 28: ...Publication No 559472 01 92 SERVICING INSTRUCTIONS Page 26 FIG 30 FAULT FINDING CHART ...