5.17 Controller Stop Mode
(Manual Adjustment of
Burner Load)
For setting and controlling the CO
2
values the Paramount in operated in the
con-
trol stop function
.
1.
> 3 s
xxxxxxxxxxxx
Press operation mode button Heating Operation for
approximately 3 seconds
=> the message
Controller Stop Function ON
is displayed.
2. Wait, until the display has reached the basic display again.
3.
Press information button
=> The message
Controller stop setpoint adjust
appears in the display. The ac-
tual modulation degree will be displayed on the display.
4. Press OK button
= > The nominal value can now be changed.
5. Press OK button
=> The displayed nominal value is taken over by the control.
Note:
The regulator stop function is stopped by pressing the
operating mode but-
ton Heating Operation
for approximately 3 seconds, reaching the maximum boiler
temperature or a time limit.
If a heat demand from a cylinder with internal indirect coil is present, this demand
will continue to be met while the controller stop function is running.
5.18 Guide Values for Injector
Pressure
Guide values for gas flow, jet presure and CO
2
-content
The values given in
Tab. 6 (Page 36)
are guide values. It is important that the gas
quantity is set via the injector pressure in such a way that the CO
2
-value is within
the specified values (see
Tab. 2 (Page 13)
).
Installation
7308272-03 03.14
Paramount three 30-115 kW
35
Summary of Contents for Paramount 40
Page 1: ...Installation manual Gas condensing boiler Paramount three 30 115 kW ...
Page 23: ...Prior to installation 7308272 03 03 14 Paramount three 30 115 kW 23 ...
Page 25: ...Fig 5 Connection plan Prior to installation 7308272 03 03 14 Paramount three 30 115 kW 25 ...
Page 28: ...4 9 Legend Prior to installation 28 Paramount three 30 115 kW 7308272 03 03 14 ...