![Potterton Paramount 40 Installation Manual Download Page 112](http://html.mh-extra.com/html/potterton/paramount-40/paramount-40_installation-manual_1583071112.webp)
Central setp compensation
(6117)
The central setpoint lead monitors the heat generator setpoint to the required
central flow temperature. With the setting the maximum corrector is restricted,
even if a large adaptation is required.
Frost protection plant
(6120)
The heating circuit pump will be activated by the outside temperature without
heat request If the outside temperature reaches the lower setpoint of -4°C,the
heating circuit pump will be activated. If the outside temperature is between -5°C
and +1.5°C, the pump will be activated every 6 hours for 10 minutes. When reach-
ing the upper limit of 1.5°C, the pump will be switched off.
Saving sensors
(6200)
Sensor statuses can be stored under programme number 6200. This happens au-
tomatically; however, after changing the plant (removal of a sensor) the state at
the sensor terminals must be stored new.
Reset to default parameters
(6205)
The factory settings of the control unit will be written to the control unit.
Caution!
The control parameters will be overwritten. The factory settings are stor-
ed in the control unit.
- Activation of the prog. no. 6205:
The control will be reset to the
factory settings
.
Control numbers generator
1/storage/heating circuit
(6212, 6213, 6215, 6217)
The basic device generates a control number for identification of the plant
scheme, which is composed of the numbers listed in
Tab. 11 (Page 112)
Tab. 11: Check no. heat source 1 (prog.-no. 6212)
Solar
A collector field with sensor
B6
and collector pump
Q5
Tank charging pump for buffer storage tank
K8
Solar diverting valve for buffer storage tank
K8
Solar charging pump for swimming pool
K18
Solar diverting valve for swimming pool
K18
External solar exchanger, Solar pump
K9
DHW=DHW storage tank B=Buffer storage tank
0
No solar
1
*
3
DHW/B
5
X
6
X
8
X
DHW+B
9
X
DHW/B
10
X
DHW
11
X
DHW
Programming
112
Paramount three 30-115 kW
7308272-03 03.14
Summary of Contents for Paramount 40
Page 1: ...Installation manual Gas condensing boiler Paramount three 30 115 kW ...
Page 23: ...Prior to installation 7308272 03 03 14 Paramount three 30 115 kW 23 ...
Page 25: ...Fig 5 Connection plan Prior to installation 7308272 03 03 14 Paramount three 30 115 kW 25 ...
Page 28: ...4 9 Legend Prior to installation 28 Paramount three 30 115 kW 7308272 03 03 14 ...