2. Pull off the lead at the generator, then unclip the lead from the two clips beneath the combustion
chamber.
3. Replacement is the reverse of removal.
CAUTION: When fitting the replacement lead, ensure that the end with the clear insulation is connected to
the electrode and that with the black insulation connected to the generator.
4. Test the boiler as described in
6, ‘Final Adjustment’
BOILER DATA
Information concerning Boiler setting data can be found in
Table 1
.
8. FAULT FINDING
As well as the fault finding chart given, reference should also be made to the wiring diagrams
Figure 6
. For
electrical faults check Figures
15
,
16
and
17
. Electrical procedures described are in accordance with the
Instruction for Gas Multi-meter booklet.
CONDITION
POSSIBLE CAUSE
REMEDY
(1) No gas supply.
Check all cocks are open in
the supply to the boiler.
(2) Control button not pressed
fully down.
Control button must be
pressed fully down.
(a) Remove plastic electrical
terminal cover from top of gas
control valve by unscrewing
the screw.
(b) Remove the four screws
securing the solenoid valve to
the top of the control valve.
A. Pilot fails to light.
(3) Blocked pilot filter
(c) Lift off the solenoid valve
and the gasket beneath.
Page 19
Service Section – Page 20
CONDITION
POSSIBLE CAUSE
REMEDY
(d) Unscrew and remove the
single screw securing the flat
plate to the main valve body,
then lift off the plate and the
gasket beneath.
(e) Lift out the filter and
replace as necessary.
(f) Re-assemble in the reverse
order.
4) Blocked pilot injector.
Remove and change the
injector as described in
Maintenance Instructions
Section 7.b.
Summary of Contents for Flamingo RS40
Page 6: ...FIG 2 PRESSURE LOSS ACROSS BOILER Page 4 DATA SECTION Page 5 ...
Page 14: ...FIG 8 GRAVITY HOT WATER WITH TEMPERATURE CONTROLLED AND PUMPED CENTRAL HEATING ...
Page 18: ...Page 13 ...
Page 29: ...FIG 15 F F D AND THERMOCOUPLE Page 21 Service Section Page 22 FIG 16 SOLENOID VALVE ...
Page 31: ...Back page Page 23 ...