background image

PRINTED IN USA

MFg. #5401205 - REV H

01/12

 PAgE 4 OF 4

vsr-sG

vane type waterflow

alarM swItCH wItH retarD 

anD Glue-In unIon

Removal of Waterflow Switch
•  

To prevent accidental water damage, all control valves should be shut tight and the system completely drained before waterflow detectors are 

removed or replaced.

•  Turn off electrical power to the detector, then disconnect wiring.
•  Loosen nuts and seperate unit from the glued-in fittings
•  Gently lift the unit far enough to get your fingers under it.  With your fingers, roll the vane so it will fit through the hole while continuing to lift 

the waterflow detector.  

 

 

 

 

 

 

 

 

 

 

 

•  Lift detector clear of pipe.

for CpvC pIpe

fig. 9

retard/switch assembly replacement 

(See Fig. 9)

  The Retard/Switch Assembly is field-replaceable without draining the system or removing the waterflow switch from the 

pipe

Make sure the fire alarm zone or circuit connected to the waterflow switch is bypassed or otherwise taken out of service.  

1. 

Disconnect the power source for local bell (if applicable).

2. 

Identify and remove all wires from the waterflow switch.

3. 

Remove the (2) mounting screws holding retard/switch assembly to the base. 

4. 

Do not

 remove the (2) retard housing screws. 

Remove the retard assembly by lifting it straight up over the tripstem. 

5. 

Install the new retard assembly. Make sure the locating pins on the retard/switch assembly fit into the locating pin bosses on the base. 

6. 

Re-install the (2) original mounting screws.

7. 

Reconnect all wires. Perform a flow test and place the system back in service. 

8. 

Maintenance

Inspect the waterflow switch monthly.  If leaks are found, replace the waterflow switch.  The VSR-SG waterflow switch should provide years of 

trouble-free service. The retard and switch assembly are easily field replaceable. In the unlikely event that either component does not perform 

properly, please order replacement retard switch assembly stock #1029030 (see Fig. 9). There is no maintenance required, only periodic testing 

and inspection.

DWG# 1190-2

BREAK OUT ThIN SECTION OF COVER 

WhEN  WIRING  BOTh  SWITChES 

FROM ONE CONDUIT ENTRANCE.

Do not

 REMOVE 

(2) RETARD hOUSING 

SCREWS

REMOVE (2) ORIGINAL MOUNTING 

SCREWS hOLDING RETARD/SWITCh 

ASSEMBLY TO BASE

RETARD/SWITCh ASSEMBLY

(2) ORIGINAL MOUNTING 

SCREWS

(2) LOCATING PINS

(2) LOCATING PIN 

BOSSES IN BASE

BASE

Summary of Contents for VSR-SG

Page 1: ...fications subject to change without notice Stock Number 1144460 Optional Cover Tamper Switch Kit stock no 0090148 Replaceable Components Retard Switch Assembly stock no 1029030 Enclosure The VSR SG switches and retard switch are enclosed in a general purpose die cast housing The cover is held in place with two tamper resistant screws which require a special key for removal A field installable cove...

Page 2: ...duce a minimum flow of 10 GPM to activate the switch The discharge orifice shall be equal to the smallest sprinkler used in the system Fig 2 Important 11 paddles are furnished with each unit to accommodate the various sizes and manufacturers of TEES The paddles have raised lettering that show the pipe size and the TEE manufacturer they are to be used with The proper paddle must be used The paddle ...

Page 3: ...lowing water activates switch in one direction only DWG 1205 15 DWG 1190 1 5 56 in 141 2 mm PIPE PLASTIC PADDLE 2 00 in 50 8 mm 3 91 in 99 33 mm 3 50 in 89 0 mm An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections The wire must be severed thereby providing supervision of the connection in the event that the wire become dislodge...

Page 4: ... wires from the waterflow switch 3 Remove the 2 mounting screws holding retard switch assembly to the base 4 Do not remove the 2 retard housing screws Remove the retard assembly by lifting it straight up over the tripstem 5 Install the new retard assembly Make sure the locating pins on the retard switch assembly fit into the locating pin bosses on the base 6 Re install the 2 original mounting scre...